Grounding Specifications
To work with interior connections
1. Connect all grounding and bonding conductors that are connected above grade or
interior to a building using two-hole multiple crimp type (with UL tool and
circumferential die compression) connections or by exothermic weld connections
where allowed.
2. Size AC service electrical ground per the NEC with No. 2 AWG BTCW minimum.
3. Run service ground wire continuously and in an unbroken manner.
110 TDC-0971-011 CCU 100 and Repeater 100 Installation Guide