The annunciator icon indicators represent the following:
Indicates when the measured battery voltage is lower than the
programmed threshold, or the cumulative power failure duration
exceeds three years.
Indicates when the meter has detected an active alarm condition.
Indicates when the calculated demand value is higher than the
programmed threshold.
Indicates that there is active communication in progress between the
meter and an external device.
Each of the three icons represent a connected phase.
If a phase is missing, the associated icon is not lit.
If voltage sags or swells occur on a phase, the associated
icon will blink.
The four individual arrow icons indicate the direction and type of the
energy currently measured by the meter.
Active and Reactive
Import and Export
If the incoming supply phase-sequence is incorrect (e.g. 1,3,2) these
icons flash.
The following examples show the effect meter configuration parameters such as scaler, number of digits and
decimal places, have on the display.
Example 1
The energy channel configured in Wh and the value is 123 456 789 Wh.
Depending on the scaler value the reading via COSEM read out would be:
123456789*Wh
123456,789*kWh