9.7. Cabling
The meter is factory-configured for either asymmetrical (VDE) or symmetrical (USE) wiring and the main terminal
design and specification is different for Direct and Transformer connection meter types.
Main terminal wiring - transformer connection
VDE wiring
Terminal
Function
Terminal
Function
Terminal
Function
Terminal
Function
1
I1 in
4
I2 in
7
I3 in
11
Neutral
2
U1 in
5
U2 in
8
U3 in
14
APS
3
I1 out
6
I2 out
9
I3 out
15
APS
USE wiring
Terminal
Function
Terminal
Function
Terminal
Function
Terminal
Function
1
I1 in
4
U2 in
7
Neutral
11
I1 out
2
U1 in
5
I3 in
8
I3 out
14
APS
3
I2 in
6
U3 in
9
I2 out
15
APS
Main terminal wiring - direct connection
Terminal
Function
Terminal
Function
Terminal
Function
Terminal
Function
1
I1 in
4
I2 in
7
I3 in
10
Neutral
2
U1 in
5
U2 in
8
U3 in
13
APS
3
I1 out
6
I2 out
9
I3 out
14
APS
Main terminal specification
Terminal type
Clamp screws
Cable diameter
Meter type
Voltage
2 x M4
5mm (max)
Transformer
Current
2 x M4
5mm (max)
Transformer
Voltage
2 x M3
3.2mm (max)
Direct