www.janitza.com UMG 96-S2
13
3.6 Performance features
General information
· Integrated front panel unit with the
dimensions 96 x 96 mm.
· Connection via pluggable screw terminals.
· Operation via 2 keys.
· Password protection
· 3 voltage measurement inputs (300V CATIII).
· 3 current measurement inputs for current
transformer.
· RS485 interface (Modbus RTU, slave,
up to 38.4 kbps).
· 1 digital output (electrically isolated).
Measurement uncertainty
· Active energy, measurement uncertainty class
0.5S for ../5A transformer.
· Active energy, measurement uncertainty class
1 for ../1A transformer.
· Reactive energy, class 1.
Measurement
· Measurement in TN and TT networks
· Measurement in networks with rated voltages
up to L-L 400 V and L-N 230 V.
· Current metering range 0.005 .. 6 Arms
· True effective value measurement (TRMS)
· Continuous scanning of the voltage and
current measurement inputs.
· Frequency range of the mains frequency
45 Hz .. 65 Hz.
· Measurement of harmonics 1st through 15th
for U
LN
and I.
· U
LN
, I, P (consumption/export), Q (ind./cap.).
· Recording of more than 800 measured values.
· Fourier analysis 1st to 15th harmonics for
U and I.
- 2 rates (switchover via Modbus).

Table of Contents

Other manuals for janitza UMG 96-S2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the janitza UMG 96-S2 and is the answer not in the manual?

janitza UMG 96-S2 Specifications

General IconGeneral
Brandjanitza
ModelUMG 96-S2
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals