What to do if the indirect-fired burner doesn’t light on Johnson Controls Industrial Equipment?
- KKenneth McconnellSep 10, 2025
If the indirect-fired burner in your Johnson Controls Industrial Equipment doesn’t light, check the heat setpoint and the OA lockout setpoint (the lockout should be above the OA temperature). Ensure the MOA module is in AUTO (green light indicates it's on, red light indicates a blown fuse). Check the blower on the burner and any lockout alarms on the Honeywell control. Inspect the burner airflow switch, the low fire end switch on the burner damper motor, the spark rod and flame rod, and the pilot assembly.