Fit
Display Short Meaning
Expert
Mode Description
Monitor DNER Data Not
Expecting Reply
X Displays the number of data
frames sent by the device that do
not require an immediate reply.
This value includes proprietary
frames that have been sent and
received a reply.
Monitor Treply Time to Reply X Max milliseconds (ms) to reply
with token after receiving a token.
Must be <25 ms.
Monitor Tder Response Time
to DER
X Max ms to respond to a
DataExpectingReply. Must be <250
ms.
Monitor Tpostp Response Time
Postponed
X Max ms to respond to
DataExpectingReply with
ReplyPostponed. Must be <250
ms.
Monitor Tusage Total Wait RPFM X Max ms waits for a
ReplyToPollForMaster or Token
retry. Must be >20ms and
<100ms.
Monitor Trpfm Response Time
PFM
X Max ms to respond to PFM with
RPFM. Must be <25 ms.
Monitor Retry Retries X Displays the number of times the
device tried to pass a token as the
next node did not start using it
within the time allowed by BACnet
protocol.
Monitor MaxMst Max Master X Highest destination address
during PFM. Default is 127.
Normally, when all controllers
have power and a ScanBus is
executed, the address seen listed
is the next address in the loop
(Address 10 passed to Address 11,
so it will show 11).
Monitor MaxFrm Max info Frames X Maximum number of frames from
this address.
Monitor Npoll Tokens between
PFM
X Number of Tokens between Poll-
For-Master.