Table 29: Cooling performance data - 3 ton - indoor coil: XAFB36DXXN1
IDCFM 950 1150 1350
ID DB
(°F)
80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
Air
temperature
entering
outdoor unit
(°F)
ID WB
(°F)
57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
T.C. 30.1 32.1 32.4 35.7 39.8 32.1 33.3 33.6 37.0 41.1 34.0 34.5 34.7 38.2 42.4
S.C. 30.1 28.6 24.2 24.6 20.1 32.1 31.6 26.7 27.1 22.0 34.0 34.5 29.1 29.6 23.8
85
kW 2.80 2.80 2.80 2.78 2.77 2.86 2.86 2.87 2.86 2.85 2.93 2.93 2.94 2.93 2.93
T.C. 29.3 30.9 31.0 34.3 38.3 31.1 32.0 32.0 35.4 39.5 32.9 33.1 33.0 36.5 40.7
S.C. 29.3 28.2 23.7 24.0 19.7 31.1 31.0 26.0 26.6 21.5 32.9 33.1 28.3 29.1 23.3
95
kW 3.08 3.08 3.08 3.07 3.07 3.15 3.15 3.15 3.15 3.15 3.22 3.22 3.23 3.22 3.23
T.C. 27.8 29.1 29.2 32.5 36.2 29.5 30.2 30.1 33.5 37.3 31.2 31.3 31.1 34.5 38.5
S.C. 27.8 27.3 22.9 23.4 19.0 29.5 29.7 25.2 25.9 20.7 31.2 31.3 27.4 28.4 22.5
105
kW 3.57 3.59 3.59 3.55 3.53 3.63 3.64 3.65 3.62 3.61 3.68 3.69 3.71 3.69 3.69
T.C. 26.4 27.4 27.4 30.8 34.1 28.0 28.5 28.3 31.7 35.2 29.6 29.6 29.2 32.6 36.3
S.C. 26.4 26.5 22.2 22.8 18.3 28.0 28.4 24.4 25.2 19.9 29.6 29.6 26.6 27.7 21.6
115
kW 4.06 4.09 4.09 4.02 3.98 4.09 4.12 4.14 4.08 4.05 4.13 4.15 4.18 4.14 4.13
Cooling performance data notes
• All capacities include indoor fan heat. kW values are for the system (outdoor + indoor).
Multipliers for determining the performance with other
indoor sections
Note: For dry bulb temperatures different than those listed (between 73°F to 87°F), sensible
capacity increases by 1060 Btu/h per 1000 CFM per degree above the listed temperature and
decreases by 1060 Btu/h per 1000 CFM per degree below the listed temperature.
Cool multiplier air handler - 3 ton
Table 30: Cool multiplier air handler - 3 ton
Air handler model Indoor coil model Total capacity Sensible capacity kW
— XAFB36D 1.00 1.00 1.00
— XAFB36E 1.00 0.99 1.00
— XAFC36D 1.00 1.00 1.00
— XAFC42E 1.00 1.00 1.00
— XAFD42E 1.00 1.01 1.00
— XAHC36D 1.00 1.00 1.00
— XAHC42E 1.00 1.00 1.00
— XAHD42E 1.00 1.01 1.00
— XAUB36D 1.00 1.00 1.00
— XAUC42E 1.00 1.00 1.00
JHVTB36DBCC2N1 — 1.00 0.95 0.94
JHVTC36DBCC2N1 — 1.02 0.97 0.93
JMET12BS2N1 XAFB36D 1.02 1.01 0.95
JMET12BS2N1 XAFB36E 1.02 1.00 0.95
JMET12BS2N1 XAUB36D 1.02 1.01 0.95
JMET12BS4N1 XAFB36D 1.02 1.02 0.97
JMET12BS4N1 XAFB36E 1.02 1.03 0.97
JMET12BS4N1 XAUB36D 1.02 1.02 0.97
JMET12CS2N1 XAFC36D 1.02 0.98 0.95
JMET12CS4N1 XAFC36D 1.01 0.95 0.94
Technical Guide: RAC Series RAC134 Models - 13.4 SEER2 Split-System Air Conditioner - Single-Phase64