EasyManua.ls Logo

Johnson Controls SNE Series - Ordering Information; SNE Ordering Information

Johnson Controls SNE Series
28 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table 23: SNE series network engine details: SNE2200x, SNE1100x, SNE1050x, SNE110Lx
Features SNE2200x SNE1100x SNE1050x
SNE110Lx
11
Supported integrations BACnet/SC
BACnet/IP
- Simplex
®
Fire Alarm Control Unit (FACU)
- Cree
®
SmartCast
®
Lighting Control
- Molex
®
Lighting Control
BACnet MS/TP Field Controller (FC) Bus
N2 Bus
Note: The M4-SNE110Lx-0 model does not support the N2 Bus.
LonWorks
®
(requires USB to LON adapter)
Note: The M4-SNE110Lx-0 model does not support the LonWorks network interface.
Modbus: Modbus TCP/IP on Ethernet and Modbus Remote Terminal Unit on RS-485
KNX IP
M-Bus
Tyco
®
C•CURE
®
9000 and victor
®
Video Management
Zettler
®
Fire Panel
OPC Unified Architecture (OPCUA/UA)
MQ Telemetry Transport (MQTT)
Operating System Wind River
®
Linux LTS 17 (LTS=long-term support)
Microprocessor NXP i.MX6 DualLite processor
Memory Flash 2GB of DDR3 RAM and 16 GB of eMMC Flash
User Interface Site Management Portal (SMP)
1 These models are intended for use with the ADS-Lite-A servers (only) in Australia, China, Hong Kong, India, Indonesia, Japan, Korea,
Malaysia, New Zealand, Philippines, Singapore, Taiwan, Thailand, Vietnam, and select branches within regions of Africa and the
Middle East.
2 Only the supported USB integration adapters function with the SNE. Other integration adapters that are not supported cannot
function with the SNE.
3 Multiple IP integrations can be on an engine, including BACnet/IP and BACnet/SC, but this is limited by the maximum devices that
can be mapped to a trunk. The total number of BACnet/IP or BACnet/SC devices that you can map is 150. You cannot map 150 IP
and 150 SC devices at the same time because they use the same BACnet Integration object.
4 Suggested object limit for performance considerations.
SNE ordering information
The SNE models listed in the following table are also available as reconditioned models. To order a reconditioned version
add an R after the product code number. In addition, the table shows three different models per cell because the newer
models are not shipped until existing stock of the older model is depleted.
Note: Since the SNE is a new model, the
reconditioned model may not be available.
SNE Installation Guide 21

Related product manuals