Configuring occupancy
To adapt to nearly any application, the TEC3000 controller
supports a wide variety of occupancy sources, such as:
• Local stand-alone weekly scheduler
• Remote schedule from BAS
• Occupancy sensor (internal or remote)
• Occupancy binary input (configurable)
• Manual occupancy override
• Temporary occupancy (by interacting with the screen
while in unoccupied mode)
• Temporary occupancy binary input
Occupancy is determined using a top-down decision
matrix as shown in Table 9.
Enumerations may not match the TEC3000 Series
Networked and Wireless Single- or Two-Stage Economizer
Thermostat Controllers Installation Guide (LIT-12013163)
and the TEC3000 Series Field-Selectable BACnet MS/TP or
N2 Networked Thermostat Controllers Technical Bulletin
(LIT-12011956) for NAE releases prior to 7.x.
Table 9: Occupancy determination
Sequence of operation (highest to lowest priority) Status indicated
Manual
Occupancy
Mode
(OCCOVRD-
MODE)
1
Occupancy BI
(BI1-S, BI2-S)
1
2, 3
Temporary
Occupancy
2
,
3
Occupancy
Schedule
(External or
Schedule)
(OCC-
CONFIG, NET-
OCC)
4
Motion
Sensor
4
Effective
Occupancy
(EFF-OCC)
Occupancy Source
(OCCSOURCE-S)
Occupied Occupied-
Override
Unoccupied
–
Unoccupied-
Override
Occ Override
Closed
1
Occupied
Open
1
– –
Unoccupied
Occupancy BI
True
2
NOT Occupied Temp
Occupancy
Temp Occ
True
3
NOT Occupied
–
Temp
Occupancy
Temp Occ BI
True Occupied
False Standby
Occupancy SensorOccupied
Disabled Occupied
Unoccupied Unoccupied
Standby
–
Standby
Occupancy Schedule
True Occupied
False Unoccupied
Occupancy Sensor
No Override
Not
Configured
1
False
5
Not Set
5
Disabled Occupied Occupancy Schedule
1 Not Configured means that neither BI1 Config nor BI2 Config is set to Occupancy BI. Open and Closed refer to the current state of
the BI when configured as Occupancy.
2 True is triggered by interacting with the screen during a scheduled unoccupied period. A value of True can only occur when the
schedule is not Occupied.
3 When triggered by a BI configured for Temp Occ, the input is ignored when the schedule is Occupied, the Manual Occupancy Mode
is not No Override, or an Occupancy BI is configured.
4 Built-in occupancy sensing (PIR) or BI configured for Motion NO or Motion NC.
5 Not Set occurs when no events are scheduled through the local scheduler, or the schedule source is set to Schedule and the
Schedule is writing Not Set as the schedule.
TEC3000 Series Networked and Wireless Single- or Two-Stage Economizer Thermostat Controllers Installation Guide20