Table 18: TEC3000 Series Networked and Wireless Single- or Two-Stage Economizer Thermostat Controllers
technical specifications
Specification Description
Power requirements 19 VAC to 30 VAC, 50/60 Hz, 4 VA at 24 VAC nominal, Class 2 or safety extra-low
voltage (SELV)
USB port power rating 120 mA to 250 mA current draw supported
Relay contact rating 19 VAC to 30 VAC, 1.0 A maximum, 15 mA minimum, 3.0 A in-rush, Class 2 or SELV
Binary inputs Dry contact across terminal COM to terminals BI1 or BI2
Analog inputs Nickel, platinum, A99B, 2.25k ohm NTC, 10k ohm NTC, 10k ohm NTC Type 3 across
terminal COM to terminals R SEN
Temperature sensor type Local digital sensor
Wire size 18 AWG (1.0 mm diameter) maximum, 22 AWG (0.6 mm diameter) recommended
For wired models: Up to 100 devices maximum for each Network Automation
Engine (NAE); 4,000 ft (1,219 m) maximum cable length. Refer to the MS/TP
Technical Bulletin for the Metasys, FX, or Verasys
®
system installed.
MS/TP network guidelines
For wireless models: Up to 100 devices maximum for each Network Automation
Engine (NAE)
Wireless band (for wireless models) Direct-sequence spread-spectrum 2.4 GHz ISM bands
ZFR 10 mW maximumTransmission
power (for
wireless
models)
ZFR Pro2 100 mW maximum
50 ft (15.2 m) recommended indoorTransmission range (for wireless
models)
250 ft (76.2 m) line of sight, maximum
Backlit display -40.0°F/-40.0°C to 122.0°F/50.0°C in 0.5° increments
Heating control 40.0°F/4.5°C to 90.0°F/32.0°C
Temperature
range
Cooling control 54.0°F/12.0°C to 100.0°F/38.0°C
Accuracy Temperature ±0.9F°/±0.5C° at 70.0°F/21.0°C typical calibrated
Minimum deadband 2F°/1C° between heating and cooling
occupancy sensor motion detection
(occupancy sensing models)
Minimum of 94 angular degrees up to a distance of 15 ft (4.6 m); based on a clear
line of sight
Operating 32°F to 122°F (0°C to 50°C); 95% RH maximum, noncondensingAmbient
conditions
Storage -22°F to 122°F (-30°C to 50°C); 95% RH maximum, noncondensing
BACnet
International
BACnet Testing Laboratories
(BTL) 135-2001 Listed BACnet Advanced Application
Controller (B-AAC)
UL Listed, File E27734, CCN XAPX, Under UL60730
Networked models: FCC Compliant to CFR 47, Part 15, Subpart B, Class B
United States
Wireless models: Transmission complies with FCC Part 15.247 regulations for low
power unlicensed transmitters; transmitter identification FCC: OEJ-WRZRADIO.
ZFR183x: Contains FCC ID: OEJZFRPRO2
UL Listed, File E27734, CCN XAPX7, Under E60730
Networked models: Industry Canada, ICES-003
Compliance
Canada
Wireless models: Industry Canada (IC) RSS-210; Transmitter identification
ZFR1810-1: IC: 279A-WRZRADIO.
ZFR183x: Contains IC: 279A-ZFRPRO2