4. Press Dehumidification and use the up and down
arrows to set the value of Humidity Setpoint.
5. Press Save and the back arrow to return to the
previous screen.
After you select the Dehumidification Sequence Mode,
perform the Aux Control configuration as described in
Setting the Aux mode when dehimidification is enabled.
These options are also exposed to BAS through the points
DEHUM-ENABLE, UNOCC DEHUM ENABLE, and DEHUM-
SEQ-MODE.
Aux control
The TEC features an auxiliary output that you can
configure to operate in a few different ways. The available
Aux Mode options depend on whether the auxiliary
output is used for dehumidification control or not.
When Dehumidification is disabled, the Aux Mode
supports the following options:
Not Used—Output is always off
Occupied NO—Output is normally open, but closes
when occupied
Occupied NC—Output is normally closed, but opens
when occupied
Occupied Fan NO—Output is normally open, but is
closed when occupied with the fan running
Occupied Fan NC—Output is normally closed, but is
open when occupied with the fan running
On—Output is turned on (relay closed), used by a BAS
to directly control the AUX output
Off—Output is turned off (relay open), used by a BAS to
directly control the AUX output
When Dehumidification is enabled, the Aux Mode
supports the following options:
Dehumidifier—select when external or auxiliary
dehumidifier is connected to Aux BO. See Figure 9 and
Figure 10.
Hot Gas Reheat—select when HGR valve is connected
to Aux BO. See Figure 11.
Setting the Aux mode when
dehimidification is disabled
About this task:
To set the Aux Mode when Dehumidification is disabled,
complete the following steps:
1. Press the Menu icon.
2. Press Setup.
3. Press General Setup.
4. Press Aux Mode and set accordingly.
5. Press Save and the back arrow to return to the
previous screen.
This option is also exposed to the BAS through the point
AUX-MODE.
Setting the Aux mode when
dehimidification is enabled
About this task:
To set the Aux Mode when Dehumidification is enabled,
complete the following steps:
1. Press the Menu icon.
2. Press Setup.
3. Press General Setup.
4. Press Aux Mode and set to Not Used.
5. Press Dehumidification Aux Mode and select
according to the equipment installed.
6. Press Save and the back arrow to return to the
previous screen.
This option is also exposed to the BAS through the point
DEHUM-AUX-MODE.
Scheduled circulation
About this task:
You can schedule to run your fan for a minimum duration
per hour during occupied or unoccupied hours. If the
minimum hourly fan runtime is not exceeded, the fan
turns on at the end of the hour for the length of time
required to fulfill the minimum run time. The fan runtime
calculation includes runtime initiated when the Fan Mode
is set to On and other overrides. The fan does not turn
on if the fan runtime is already longer than the minimum
hourly fan runtime. When you enabled the Scheduled
Circulation Only When Occupied setting, the fan does
not turn on at the end of the hour to fulfill the minimum
runtime unless the occupancy state is set to Occupied.
To set the Scheduled circulation, complete the following
steps:
1. Press the Menu icon.
2. Press Setup.
3. Press General Setup.
4. Press Scheduled Circulation and select Enable
5. Press Minimum Hourly Fan Runtime and set the
time in a range of 5 to 30 minutes.
6. Press Fan Circulation Speed and set the fan speed.
7. Press Scheduled Circulation Only When
Occupied and select Disable or Enable as desired.
8. Press Save and the back arrow to return to the
previous screen.
This option is also exposed to the BAS through the points
SCH-CIR-EN, SCH-CIR-ONLYOCC, and MIN-HR-FAN. If
Scheduled Circulation is disabled, the other two objects
show unreliable.