Page #61 background imageLoading...
Page #61 background image
61
JOHNSON CONTROLS
FORM 145.05-NOM1 (708)
INPUT
To use the INPUT screen use the right arrow key >
to move to [INPUT] and press the ENTER key. Use
the right > or left arrow key < to scroll through the
following data:
Analog In
Supply Air Temp – ° F
Supply Air Hum – % RH (FlexSys units only)
Supply Air Dew – ° F (FlexSys units only)
Mixed Air Temp – ° F
Return Air Temp – ° F
Coil Leav Temp – 0° F (FlexSys units only)
Slab Temp – 0° F (FlexSys units only)
Outside Air Temp – 0° F
In Water Temp – ° F
Out Water Temp – ° F
Fan Speed – %
Floor Static – "wc (FlexSys units only)
Coil Dif Static – "wc (FlexSys units only)
# Duct Sensors – 1 or 2
Duct Static 1 – "wc
Duct Static 2 – "wc
Calc Duct Stati – “wc
# Of Comp – 2 or 4
# Of Stages – 2, 3, 4, or 6
Comp A Disch – psig
Comp A Suct – psig
Comp B Disch – psig
Comp B Suct – psig
Comp C Disch – psig
Comp C Suct – psig
Comp D Disch – psig
Comp D Suct – psig
Digital In
DDC On Switch – On or Off
DDC Off Switch – On or Off
Safe Input – On or Off, On = OK
Air Flow Switch – On or Off, On = OK
Duct Hi Static – On or Off, On = OK
Freeze Stat – On or Off, On = OK
Dirty Filter – On or Off, Off = OK
OUTPUTS
To use the OUTPUTS screen use the right arrow key
> to move to [OUTPUTS] and press the ENTER key.
Use the right > or left arrow key < to scroll through the
following data:
Analog Out
B/P Damp Mod 0.0 to 10.0 V (FlexSys units
only)
Cond Vlv Mod – 2.0 to 10.0 V
VFD Mod – 0.0 to 10.0 V
ΟΑ Econ Mod – 2.0 to 10.0 V
Water Econ Mod – 2.0 to 10.0 V
PID Loop Out
AC S/A Temp – %
AC R/A Temp – %
AC S/A Dew – % (FlexSys units only)
AC DX Temp – % (FlexSys units only)
Econ S/A Temp – %
Econ R/A Temp – %
Econ S/A Dew – % (FlexSys units only)
DX B/P S/A Tmp – % (FlexSys units only)
DX B/P Press – % (FlexSys units only)
Cond PID – %
Heat PID – %
Digital Out
CV Fan Enable – On or Off
VAV Fan Enable – On or Off
Cond. Pump Out – On or Off
Fan Output – On or Off
VAV Box Output – On or Off
Comp A En – On or Off
Comp B En – On or Off
Comp C En – On or Off
Comp D En – On or Off
Alarm Out – On or Off
6

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls York VERSECON YSWD Series and is the answer not in the manual?

Johnson Controls York VERSECON YSWD Series Specifications

General IconGeneral
BrandJohnson Controls
ModelYork VERSECON YSWD Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals