7 Configuration level
7.8 Display/Operation/Service counter
Both displays can be adapted to the respective requirements by the
configuration of the displayed value, the decimal place and the
automatic change (timer).
The time-out of the operation, the function key assignment and the
level inhibit can also be configured.
ConF -> diSP ->
Parameters Value/
Selection
Description
Upper display
d iSU
(analog
selector)
Process
value
Display value for the upper display
Lower display
d iSL
(analog
selector)
Current
set point
value
Display value for the lower display
Display change
to timer value
diSt
0
1
2
Time appears in the lower display (only
effective after the timer is started)
no function
Display of residual timer time
Display of timer run time
Time-out
tout
0…180…
255
Time period in seconds, after which the
device automatically returns to normal
display if no key is pressed.
Restart time
trES
(Power ON delay)
0…9999 Start delay time in seconds after Power ON
All functions of the device are only active
after this time has elapsed.