Junos OS Evolved systems, such as QFX5200-32C-L are based on a new alarm infrastructure, not all
power supplies and fan alarms are supported. Table 44 on page 155 shows these alarms.
Table 44: Chassis Alarm Messages for QFX5200-32C-L
Component Alarm Type CLI Message Recommended Acon
Fans Red (major)
Fan Tray
fan-tray-number
Absent
Install fan modules in the slots
where they are absent.
Fan Tray
fan-tray-number
Failure
Remove and check fan module for
obstrucons. Reinsert the fan
module. If the problem persists,
replace the fan module.
Yellow (minor)
FAN
fan-number
Fan Sensor Fail
Remove and check fan module for
obstrucons. Reinsert the fan
module. If the problem persists,
check the system log for the
message related to the sensor and
report the message to customer
service.
Power Supplies Red (major)
PEM
pem-number
Not Powered
Install a power supply into the
empty slot and ensure the power
supply is powered.
Temperature
sensors
Major (red)
FPC 0 Temperature Hot
Check environmental condions
and alarms on other devices. Ensure
that environmental factors (such as
hot air blowing around the
equipment) do not aect the
temperature sensor. if the condion
persists, the device might shut
down.