KaControl for Door Air Curtains
INSTALLATION AND OPERATING INSTRUCTIONS
45
Door air curtains 1.96
Function Settings Min Max Unit Comment
P098
Actuation 0..10V: Switching on limit
Valves 30 0 100 V/10
P099
Actuation 0..10V: Switching on limit
Minimum fan speed
40 0 100 V/10
P100
Actuation 0..10V: Switching on limit
Maximum fan speed 90 0 100 V/10
P101
Valve actuation by means of pulse width modulation
P-band in Heating mode
15 0 100 °C/10
P102 Default value must be set 15 0 100 °C/10
P103
Valve actuation by means of pulse width
modulation
Reset time of PI controller
If P103=0 a PI controller is enabled.
Recommended reset time when using a PI
controller: Reset time = 13 minutes
0 0 20 minutes
P104
Valve actuation by means of pulse width modulation
Minimum switching on time for the heating value in
PWM mode
0 0 20 minutes
P105 Default value must be set 50 0 -- -
P106 Default value must be set 50 0 - -
P107 Default value must be set 5 0 255 minutes
P108 Default value must be set 240 35 255 minutes
P117 Function buttons: Locking and enabling 0 0 7 -