This function protects the frequency inverter against switch off through overcurrent
during constant output frequency. When exceeding the adjusted value, the output
frequency is reduced until the value drops below the adjusted value. CP. 3 displays
"SSL" at active function.
Adjustment range: 0...200 % (off)
Resolution: 1 %
Factory Setting: 200 % (off)
t
f
set
f
real
on
off
on
off
CP.25
CP.24
LAD-stop
Current limit
t
t
t
Max. constant current
Utilization
This function protects the frequency inverter against switching off through overcurrent
during the acceleration ramp. When the ramp reaches the adjusted value,it is stopped
so long until the current decreases again. CP.3 displays "LAS" at active function.
Adjustment range: 0...200 %
Resolution: 1 %
Factory setting: 140 %
Max. ramp current