6.1.2 Connection of the shield connection
Cable shields must not be used for power supply.
A cable shield must not assume the function of an N or PE conductor.
Always lay cable shields over a large surface.
Do not extend the cable shield by unshielded wire connections to the earthing point.
This reduces the shielding effect by up to 90 %.
Lay the cable shield over a large surface directly after the entry point of the control
cabinet.
6.1.3 Connection of the protective earth
The drive converter or the control cabinet in which the drive converter is installed
must be connected to protective earth at the installation site.
Use a protective earth conductor that corresponds at least half the cross-section of
the cables used to supply the power terminals.
An earthing stud is provided at the drive converter for connecting the motor protec-
tive earth.
Theresistanceoftheprotectiveearthshouldbe0.1Ωorless.
According to EN 61800-5-1, the minimum cross-section of the protective earth con-
ductor must comply with the local safety regulations for protective earth conductors
for equipment with high leakage current.
WARNING
Indirect contact
Only with a correctly connected protective earth conductor the device
fulllstherequirementsforprotectionagainstindirectcontact.
64
ELECTRICAL INSTALLATION

Table of Contents

Other manuals for KEB COMBIVERT F5

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KEB COMBIVERT F5 and is the answer not in the manual?

KEB COMBIVERT F5 Specifications

General IconGeneral
CategoryDC Drives
Enclosure RatingIP20
Control ModeVector Control, V/f Control
ProtectionOvercurrent, Overvoltage, Undervoltage, Overtemperature, Short circuit
Fieldbus CommunicationPROFIBUS, CANopen
Communication InterfacesRS-485
Input Voltage380-480V AC
Cooling MethodForced air cooling (fan)

Related product manuals