Page3.2 - 10 COMBIVERT R6-N © KEB, 2015-07
Operating and appliance data
Parameter Addr. R PG E Min. value Max. value Res. [?] Default
ru.39 OL counter display 0227h ro - - 0 100 1 % -
In order to prevent „E.OL“ - errors by overload (load reduction in due time), the internal count of the OL coun-
ter can be made visible with this display. At 100% the
COMBIVERT switches off with error „E.OL“. The error can be reset only after a cooling time (blinking display
„E.nOL“).
Parameter Addr. R PG E Min. value Max. value Res. [?] Default
ru.40 Power on counter 0228h rw - - 0 65535 1 h -
The power on counter displays the time the inverter was switched on. The displayed value comprises all op-
erating phases. On reaching the maximum value (approx. 7.5 years) the indication remains on the maximum
value.
Parameter Addr. R PG E Min. value Max. value Res. [?] Default
ru.41 Modulation on counter 0229h rw - - 0 65535 1 h -
The modulation on counter displays the time the COMBIVERT was active (power modules controlled). On
reaching the maximum value (approx. 7.5 years) the indication remains on the maximum value.
Parameter Addr. R PG E Min. value Max. value Res. [?] Default
ru.43 Timer 1 display 022Bh rw - - 0 655,35 0,01 - -
The count of the free-programmable timer 1 is displayed. The display is done either in seconds, in hours or
in slopes/100 (see LE.21). The counter can be adjusted to any chosen value by keyboard or bus. The pro-
gramming of the counter is done with parameters LE.17...LE.21.
Parameter Addr. R PG E Min. value Max. value Res. [?] Default
ru.44 Timer 2 display 022Ch rw - - 0 655,35 0,01 - -
The count of the free-programmable timer 2 is displayed. The display is done either in seconds, in hours or in
slopes/100 (see LE.26). The counter can be adjusted to any chosen value by keyboard or bus. The program-
ming of the counter is done with parameters LE.22...LE.26.
Parameter Addr. R PG E Min.
value
Max. value Res. [?] Default
ru.68 Rated DC voltage 0244h ro - - 0 1000 1 V -
This parameter displays the rated DC voltage automatically determined by the inverter. The value is measured
at switch-on.