Page3.2 - 18 COMBIVERT R6-N © KEB, 2015-07
Operating and appliance data
Bit Value Description
0..7
1:I1
Display of the internal input terminal status (input terminals and software inputs after
the input processing block). Corresponds to the display in ru.22 „internal input state“
2:I2
4:I3
8:I4
16:IA
32:IB
64:IC
128:ID
8..15
256:O1
Display of the state of the output terminals and the software outputs (digital outputs
after the output proccessing block). Corresponds to the display in ru.25 „output termi-
nal state“
512:O2
1024:R1
2048:R2
4096:OA
8192:OB
16384:OC
32768:OD
Parameter Addr. R PG E Min. value Max. value Res. [?] Default
SY.43 Control word long 002Bh KB - + -2147483648 2147483647 1 - 0
The control word is used for status control of the inverter via bus. The control word long (SY.43) consists of the
two 16 bit parameters control word high (SY.41) and control word low (SY.50). The status word is bit-coded.
Parameter Addr. R PG E Min. value Max. value Res. [?] Default
SY.44 Status word long 002Ch ro - - -2147483648 2147483647 1 - 0
The current condition of the COMBIVERT can be readout with the status word. The status word long (SY.44)
consists of the two 16 bit parameters status word high (SY.42) and status word low (SY.51). The status word
is bit-coded.
Parameter Addr. R PG E Min. value Max. value Res. [?] Default
SY.50 Control word low 0032h rw - + 0 65535 1 - 0
The control word is used for status control of the inverter via bus. The control word long (SY.43) consists of
the two 16 bit parameters control word high (SY.41) and control word low (SY.50). The status word is bit-cod-
ed.
Bit Function Value Description
0
Control re-
lease
1:ST
This bit is only effective if di.01 „select signal source“ bit 0 is set.
Then the AND operation of this bit with di.02„digital input setting“
bit 0 is valid.
1 Reset 2:RST
An error reset is executed when changing from not activated (0)
to activated (2).
2 Start / stop
0:Stop
Direction of rotation release or the „start “(„run “) command can
be given via the control word, if oP.01 „rotation source“ contains
the values 6, 8, 9 or 10.
4:Start
continued on the next page