EasyManua.ls Logo

Keithley 6517A - Figure 2-77 Limits Bar Graph Example

Keithley 6517A
343 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Front Panel Operation
2-119
STROBE-CONTROL
This menu item enables or disables the use of digital output
#4 as a binning strobe signal.
If enabled, the strobe signal is set TRUE for greater than 10
microseconds after all limit tests have been performed on a
new reading. The FALSE to TRUE transition can be used to
trigger an external device handler to check digital outputs
#1-3 for sorting parts into bins.
When binning is enabled from the front panel or with the bus
command :CALCulate3:BSTRobe:STATe ON, the binning
strobe signal is set to FALSE. When binning is disabled, the
strobe signal is left unchanged.
DISABLED: Use this selection to disable strobe control.
ENABLED: Use this selection to enable strobe control.
PASS-PATTERN
This item allows you to program the on/off states of the dig-
ital output lines for when all limit tests pass. Note that when
the binning strobe is enabled, digital output line #4 cannot be
used.
Selecting PASS-PATTERN displays the digital output pat-
tern that occurs when all limit tests pass. To change the pat-
tern, use the cursor keys and the range keys. The range keys
toggle the parameter values between OFF and ON.
Limits example
This example sorts a quantity of 100kΩ resistors into five
bins, according to the following tolerances:
•Values less than 90kΩ (outside -10% tolerance).
•Values greater than 110kΩ (outside +10% tolerance).
•Values between 90kΩ and 99kΩ (meets -10% toler-
ance).
•Values between 101kΩ and 110kΩ (meets +10% toler-
ance).
•Values between 99kΩ and 101kΩ (meets ±1% toler-
ance).
The desired test is shown in Figure 2-78. Use the following
procedure to program the limits:
1. From the LIMITS menu, set the limit values and actions
according to the following table:
2. Enable the binning strobe signal from the STROBE-
CONTROL item of the LIMITS menu.
3. Set a pass pattern of all lines off from the PASS PAT-
TERN item of the LIMITS menu.
4. Enable the control of the digital output lines by limit set
#1 and limit set #2 from the LIMIT SET #1 and LIMIT
SET #2 menus. This sets the digital output lines to the
“pass pattern” (all OFF in this example). Since binning
is enabled, digital output #4 is also OFF.
Note that the actual state (high or low) of the digital output
lines depends on the polarity (ACTIVE-HIGH or ACTIVE-
Figure 2-77
Limits bar graph example
LLIM1 | | | | | HLIM1
Low Limit #1
Average of midpoint
and Low Limit #1
High Limit #1
Average of midpoint
and High Limit #1
Midpoint of Low Limit #1
and High Limit #1
A. Defined points of display
Reading Pass/Fail indication
-0.2836 V PASS
NOTES : 1. Press INFO to view the programmed Low Limit #1 and
High Limit #1 values.
2. Multiple display of limit values do not use unit prefixes
(i.e., volts not millivolts).
B. Example Display with Limits = ±1V
-1V
LLIM1 | | ===| | | HLIM1
1V
0V
30% of difference between
midpoint and Low Level #1
Limit Value Action
LOLIM1
HILIM1
LOLIM2
HILIM2
90kΩ
110kΩ
99kΩ
101kΩ
DIGOUT1=ON, others OFF
DIGOUT2=ON, others OFF
DIGOUT1=ON, DIGOUT2=ON,
others OFF
DIGOUT3=ON, others OFF

Table of Contents