32 Section 3 Controller TP-6844 1/13
3.3.4 Controller Parameter Table
Figure 3-9 on the following pages lists controller
parameters that are visible in SiteTech. Parameters
marked Read Only are not user-adjustable.
Some parameters that are visible in SiteTech do not
apply to the Model 6VSG generator sets. Those
parameters are not listed in the table.
The table indicates the following:
• The group in SiteTech that contains the parameter
• Factory default settings
• Units for the setting (e.g., rpm)
• Adjustment range for user-adjustable settings
Figure 3-9
SiteTech Group Parameter Units
Adjustment
Range * Default Setting
Identity Vendor Read Only Kohler Company
Identity Product Read Only VSG
Identity Firmware Version Read Only N/A
Engine Metering Engine Speed R/min Read Only N/A
Engine Metering Engine Target Speed R/min Read Only N/A
Engine Metering Battery Voltage V Read Only N/A
Engine Metering Lube Oil Temperature ° C Read Only N/A
Engine Metering Genset Controller Temperature °C Read Only N/A
Engine Metering Engine Low Oil Pressure Switch Read Only N/A
Engine Speed Governor Engine Speed Gain Adjustment 35–65 50
Generator Metering Generator True Percent Of Rated Power % Read Only N/A
Generator Metering Generator Voltage L1-L2 V Read Only N/A
Generator Metering Generator Voltage L2-L3 V Read Only N/A
Generator Metering Generator Voltage Average Line To Line V Read Only
Generator Metering Generator Current L1 A Read Only N/A
Generator Metering Generator Current L3 A Read Only N/A
Generator Metering Generator Current Average A Read Only N/A
Genset Info Genset Model Number Select Dropdown list:
6VSG-24V
6VSG-36V
6VSG-48V
Factory-set per
unit. See Section
3.3.2
Genset Info Genset Serial Number 0–20 characters
Genset Info Alternator Part Number 0–20 characters
Genset Info Genset Controller Serial Number 1–10 characters
Genset Info Engine Part Number 0–20 characters
Genset Info Engine Model Number CH-74
Genset Info Engine Serial Number 0–10 characters
Genset Info Genset State N/A Read Only N/A
Genset Run Time Genset Controller Clock Time Read Only
Genset Run Time Genset Controller Total Operation Time h Read Only N/A
Genset Run Time Engine Total Run Time h Read Only N/A
Genset Run Time Engine Total Run Time Loaded h Read Only N/A
Genset Run Time Engine Total Number Of Starts Read Only N/A
Genset Run Time Genset Date Time Of Last Maintenance Read Only (See
Section 2.3,
Resetting the
Maintenance
Timer)
1/1/01
12:00:00
AM
Genset Run Time Engine Run Time Until Maintenance h Read Only 100, 250