TP-6844 1/13 Section 3 Controller 35
Digital Output B5 † Digital Output B5 Event See dropdown
list in SiteTech
PIM: Engine Cool
Down Active;
Comm Kit:
Intrusion Alarm
Warning
Digital Output B6 † Digital Output B6 Value Read Only False
Digital Output B6 † Digital Output B6 Event See dropdown
list in SiteTech
PIM: Normal
Source Failure;
Comm Kit:
Reserve Oil
Empty Warning
ATS Exercise Exercise Interval Weekly or Every
Other Week
Weekly
ATS Exercise Exercise Run Duration min 10–30 20
ATS Exercise Exercise Mode Pulldown See
List
Unloaded Cycle
(2)
ATS Exercise Exercise Warning Enabled True or False True
Network Configuration DHCP Enabled True or False True
Network Configuration Static IP Address 0.0.0.0 –
255.255.255.25
5
0.0.0.0
Network Configuration Static Subnet Mask 0.0.0.0 –
255.255.255.25
5
0.0.0.0
Network Configuration Static Default Gateway 0.0.0.0 –
255.255.255.25
5
0.0.0.0
Network Configuration Static DNS Server 1 0.0.0.0 –
255.255.255.25
5
0.0.0.0
Network Configuration Static DNS Server 2 0.0.0.0 –
255.255.255.25
5
0.0.0.0
Network Configuration Server Host Name oncue.kohler.co
m
oncue.
kohler.com
Network Status IP Address Read Only 0.0.0.0
Network Status Subnet Mask Read Only 0.0.0.0
Network Status Default Gateway Read Only 0.0.0.0
Network Status DNS Server 1 Read Only 0.0.0.0
Network Status DNS Server 2 Read Only 0.0.0.0
Network Status MAC Address Read Only N/A
Network Status Connected Server IP Address Read Only 0.0.0.0
Network Status Network Connection Established Read Only False
Network Status Media Connected Read Only False
Rbus Network Rbus Active Read Only False
Rbus Network Rbus Connection Count Read Only 0
Rbus Network Rbus Net Cycle Time ms Read Only 100
Rbus Network Rbus Timeouts Read Only 0
Rbus Network Rbus Errors Read Only 0
Rbus Devices B1 Rbus Devices B1 Serial Number Read Only N/A
Rbus Devices B1 Rbus Devices B1 Type Read Only N/A
Rbus Devices B1 Rbus Devices B1 Communication Errors Read Only N/A
Rbus Devices B1 Rbus Devices B1 Communication Timeouts Read Only N/A
Rbus Devices B1 Rbus Devices B1 Modbus Id Read Only N/A
SiteTech Group Parameter Units
Adjustment