TP-6694 7/18 101Section 6 Accessories
6.1.13 Run Relay Kit
The run relay kit energizes only when the generator set
runs. Use the run relay kit to control air intake and
radiator louvers, alarms, and/or other signalling
devices. See Figure 6-28 and Figure 6-29.
See Section 6.2, Accessory Connections, for terminal
identifications.
273705
Figure 6-28 Run Relay Kit
GM67191-B
Figure 6-29 Run Relay Connections
6.1.14 Shunt-Trip Line Circuit Breaker
A shunt-trip line circuit breaker provides a 12- or 24-DC
volt solenoid within the line circuit breaker case that can
energize the trip mechanism. This feature allows the
circuit breaker to be tripped by the common fault (32A).
Connection requires a shunt-trip wiring kit and a dry
contact kit. See Figure 6-30 and Figure 6-31.
The optional common fault relay shown in Figure 6-31
as DCB1 has contacts rated at 10 amps at 28 VDC or
120 VAC and is used to trigger the shunt-trip line circuit
breaker kit.
GM67191-B
Figure 6-30 Shunt-Trip Wiring ( Standard)
GM67191-B
Figure 6-31 Shunt-Trip Relay Kit and Line Circuit
Breaker Wiring (Shown with Common
Fault/Failure Relay Kit)