TP-6694 7/1896 Section 6 Accessories
6.1.6 Key Switch
A two-position key switch is available for selected
models. Turn the key to the ON position to lock the
controller in AUTO mode. The key can be removed
when the switch is in the ON position.
GM103075
OFF/RESET AUTO RUN
1
1. Optional key switch
Figure 6-14 Optional Key Switch
6.1.7 Low Fuel (Level/Pressure) Switch
Some gas-fueled models offer a low fuel pressure
switch. The low fuel pressure switch connects to the
same controller terminal as the low fuel level switch on
diesel-fueled models. See Figure 6-15, Figure 6-16,
and Figure 6-17.
Note: The main tank or the transfer/day tank includes
the low fuel level switch. The fuel tank supplier
typically provides the low fuel level switch.
GM16088A-A/TP-6694
CONNECT TO TB1
(for warning) or TB3 (for
shutdown)
Figure 6-15 Low Fuel Switch (Level or Pressure)
GM67191-B
Figure 6-16 Low Fuel Switch Connection to
Controller Connection
Switch Rating 12 volts DC minimum, 0.5 amp minimum
Wiring Recommendation
Gauge mm (ft.)
18--20 30.5 (100)
14 153 (500)
10 305 (1000)
Figure 6-17 Switch Rating & Wiring Recommendation