TP-6694 7/18 27Section 1 Specifications and Features
1. V7/V8/V9 fuses, 1.5 Amp. (qty. 3)
GM69407
1
Figure 1-7 AC Circuit Fuses in Control Box
1. F1 1 Amp. auto-resettable
2. F2 1 Amp. auto-resettable
3. F3 12 Amp. non-replaceable
GM64345-C
1
2
3
Figure 1-8 Controller DC Fuses
1.3 Controller Logic Specifications
The controller logic specifications section is an overview
of the various features and functions of the controller.
Certain features function only when optional
accessories are connected. See Section 2, Operation,
for details.
The default selection time delays and digital outputs are
factory set and adjustable. Data entries require using a
PC and SiteTecht software. See the SiteTecht
software operation manual for details.
Inhibit Time Delay. The inhibit time delay is the time
period following crank disconnect during which the
generator set stabilizes and the controller does not
detect a fault or status event. Select the desired inhibit
time delay from 0 to 60 seconds.
TIme Delay (Shutdown or Warning). The time delay
follows the inhibit time delay. The time delay is the time
period between when the controller first detects a fault or
status event and the controller warning or shutdown
lamp illuminates. The delay prevents nuisance alarms.
Select the desired time delay from 0 to 60 seconds.
1.3.1 Status Event and Fault
Specifications
The Factory-Defined Settings List contains all status
events and faults with ranges and time delays including
items that do not have user adjustments.
Note: The engine ECM may limit the crank cycle even if
the controller is set to a longer time period.