TP-6694 7/1828 Section 1 Specifications and Features
Factory-Defined Settings List
Description
Controller Display
Message
Alarm
Horn
Fault
Lamp
Warning
S
hutdown
Write
Access
Display
Si
teTech
GenSet
Mode
Always
R
unning
S
topped
Range
Setting
Default
Selection
Time
Delay
Range
(sec.)
Default
Time
Delay
(sec.)
Engine Functions
Critically high fuel level
(diesel-powered models only) *
Fuel Level Critically
High
On W 0--100% 95% 0--10 5
ECM communications loss ECMCommErr
Shutdwn
On S Fixed 10
ECM diagnostics (multiple
inputs) [
ECM xxxxxx Warning On W
ECM diagnostics (multiple
inputs) [
ECM xxxxxx Shutdwn On S
ECM faults (address conflict) ECM Addr Err
Shutdwn
On S
ECM faults (model mismatch) ECM Mismatch
Shutdwn
On S 0--255 0
Engine over speed Eng Speed High
Shutdwn
On S S A 105--120% 115%
Engine start aid active Starting Aid Notice
Engine under speed Eng Speed Low
Shutdwn
On S S A 75--95% 85%
Fuel tank leak * Fuel Leak Warning On W
Fuel tank leak * Fuel Leak Shutdwn On S
High battery voltage Battery High Warning On W S A 110--135% 125% Fixed 10
High coolant temperature
Coolnt Temp High
Warning
On W
0--10
(0--30
inhibit)
0
(5 FAA)
(0
inhibit)
High coolant temperature
Coolnt Temp High
Shutdwn
On S
0--10
(0--30
inhibit)
0
(0
inhibit)
High fuel level (diesel-powered
models only) *
Fuel Level High
Warning
On W 0--100% 90% 0--10 5
Loss of fuel Loss of Fuel On S
Low battery voltage Battery Low Warning On W S A 80--105% 100% Fixed 90
Low coolant level * Coolant Lvl Low
Shutdwn
On S Fixed 5
Low coolant temperature
Coolant Temp Low
Warning
On W Fixed
16_C
(60_F)
0--10
(0--30
inhibit)
5
(0
inhibit)
Low cranking voltage Lo Crank Vlt Warning On W Fixed 60% Fixed 6
Low engine oil level * Oil Level Low Warning On W
Low engine oil level * Oil Level Low Shutdwn On S
Low fuel level (diesel models) * Fuel Level Low
Warning
On W 0--100% 35% 0--10 10
Low fuel level (diesel models) * Fuel Level Low
Shutdwn
On S 0--100% 5% 0--10 0
Low fuel pressure
(gas models) *
Fuel Press Low
Warning
On W
Low oil pressure
Oil Press Low Warning On W
Fixed
(Fixed
inhibit)
0
(30
inhibit)
Low oil pressure
Oil Press Low
Shutdwn
On S
Fixed
(Fixed
inhibit)
5
(30
inhibit)
* Function requires optional input sensors or is engine ECM dependent on some generator set models.
[ ECM inputs are engine-manufacturer dependent.
] Changeable only by resetting the controller with a personality profile (SiteTech 1.4 or higher).
** Denotes the default parameter range. Typically, ranges for the NiCad battery topology are slightly wider. For more details, refer to the
battery charger operation manual.
ST--Short Term, LT--Long Term