TP-6694 7/18 29Section 1 Specifications and Features
Description
Default
Time
Delay
(sec.)
Time
Delay
Range
(sec.)
Default
Selection
Range
Setting
GenSet
Mode
Always
R
unning
S
topped
Write
Access
Display
Si
teTech
Fault
Lamp
Warning
S
hutdown
Alarm
Horn
Controller Display
Message
No coolant temperature signal Temp Sig Loss
Shutdwn
On S
No oil pressure signal Press Sig Loss
Shutdwn
On S Fixed 5
Overcrank
Over Crank Shutdwn On S Fixed
(30
inhibit)
Speed sensor fault Spd Sens Flt Warning On W
General Functions
Alarm silence, 0--Auto only
(NFPA 110), 1--Always
AlarmSilenceMode S A 0--1 1
Aux. inputs 0--5 VDC, 1 analog Aux Input Warning On W 0--100% 100% 0--10 0
Aux. inputs 0--5 VDC, 1 analog Aux Input Shutdwn On S 0--100% 100% 0--10 0
Auxiliary inputs, up to 3 digital
(2 additional digital inputs
available with I/O module
option)
Aux Input Warning On W
0--10
(0--30
inhibit)
0(0
inhibit)
Auxiliary inputs, up to 3 digital
(2 additional digital inputs
available with I/O module
option)
Aux Input Shutdwn On S
0--10
(0--30
inhibit)
0(0
inhibit)
Backup parameters loaded Backup Pars Status
Battery charger 1
communication loss
Bat1CommLoss On W
Battery charger 2
communication loss
Bat2CommLoss On W
Battery charger fault *
(does not apply to charger
GM87448)
Batt Chg Flt On W
Battery charger identity conflict BatIdErr On W
Battery charger parameter
mismatch
ParMisatch On W
Battery fault Battery Flt On W
Chicago code active * Auto Locked Notice
Common fault Common Fault
Shutdwn
On S
Common warning Common Warng On W
Default parameters loaded Default Pars Warning On W
Emergency stop Emerg Stop Shutdwn On S
Enclosure temperature: high
shutdown
Enclsr Temp: High
Shutdwn
On S Fixed Active Fixed
5(20
inhibit)
Engine cooldown (delay) active Eng Cooldown Notice
Engine start delay active Start Delay Notice
Engine started Engine Start Status
Engine stopped Engine Stop Status
EPS supplying load Emerg Pwr On Notice
File system error (controller
fault)
File Error Shutdwn On S
Generator running Gen Running Notice
Input/output (optional module
board) communication loss
OB1 Com Loss On W
Internal failure Intern Error Shutdwn On S
* Function requires optional input sensors or is engine ECM dependent on some generator set models.
[ ECM inputs are engine-manufacturer dependent.
] Changeable only by resetting the controller with a personality profile (SiteTech 1.4 or higher).
** Denotes the default parameter range. Typically, ranges for the NiCad battery topology are slightly wider. For more details, refer to the
battery charger operation manual.
ST--Short Term, LT--Long Term