TP-6694 7/1830 Section 1 Specifications and Features
Description
Default
Time
Delay
(sec.)
Time
Delay
Range
(sec.)
Default
Selection
Range
Setting
GenSet
Mode
Always
R
unning
S
topped
Write
Access
Display
Si
teTech
Fault
Lamp
Warning
S
hutdown
Alarm
Horn
Controller Display
Message
Measurement Units,
0--English, 1--Metric
Measurement Display DS A 0--1 1
Metering communication loss MeterCommLos
Shutdwn
On S
NFPA 110 alarm active NFPA Alarm Notice
Not in auto (master control
buttons)
Not In Auto Warning On W
Prime power application,
0--Standby, 1--Prime
Power Type DS A 0--1 0
Remote start Remote Start Status
System ready System Ready Status
System timer failed TimerErrorNotice
Generator Functions
AC sensing loss AC Sens Loss
Warning
On W
AC sensing loss AC Sens Loss
Shutdwn
On S Fixed 3
Alternator protection Alt Protect Shutdwn On S
Ground fault input * Ground Fault Warning On W
kW overload
Total Power High
Shutdwn
On S Fixed
102%
standby,
112%
prime
Fixed 60
Locked rotor (failed to crank) Locked Rotor Shutdwn On S S A 1--5 5
Overfrequency Freq High Shutdwn On S 102--140% 110% Fixed 10
Overvoltage (each phase) Volts (L1--L2, L2--L3,
or L3--L1) High
Shutdwn
On S S A 105--135% 120% 2--10 2
Power rating Pwr Rating DS S 10--5000 275
System frequency System Freq DS S 50--60 60
System voltage System Volt DS S 110--600 208
Underfrequency Frequency Low
Shutdwn
On S 80--95% 90% Fixed
10 ST
60 LT
Undervoltage (each phase) Volts (L1--L2, L2--L3,
or L3--L1) Low
Shutdwn
On S S A 70--95% 80% 5--30 10
Voltage/phase configuration,
0--Single phase, 1--Single
phase dogleg, 2--three phase
wye, 3--three phase delta
SystemPhase DS S 0--3 2
Voltage regulator average
voltage adjustment
VR Volt Adj DS R 108--600 208
(Voltage) regulator
communication loss
RegCommLoss
Shutdwn
On S
SiteTech Read/Write Display Only
Charger Absorption Current
Termination Target (A)
S A 1–5 2
Charger Automatic Equalize
Enable
Note: Equalize is only
available with FLA/VRLA
topology selected.
S A
Active
Inactive
Inactive
* Function requires optional input sensors or is engine ECM dependent on some generator set models.
[ ECM inputs are engine-manufacturer dependent.
] Changeable only by resetting the controller with a personality profile (SiteTech 1.4 or higher).
** Denotes the default parameter range. Typically, ranges for the NiCad battery topology are slightly wider. For more details, refer to the
battery charger operation manual.
ST--Short Term, LT--Long Term