TP-6694 7/18 31Section 1 Specifications and Features
Description
Default
Time
Delay
(sec.)
Time
Delay
Range
(sec.)
Default
Selection
Range
Setting
GenSet
Mode
Always
R
unning
S
topped
Write
Access
Display
Si
teTech
Fault
Lamp
Warning
S
hutdown
Alarm
Horn
Controller Display
Message
Charger Charge Cycles
Between Auto Equalize Cycles
Note: Equalize is only
available with FLA/VRLA
topology selected.
S A 0–99
Charger Custom Profile Enable
S A
Active
Inactive
Inactive
Charger Depleted Battery
Current Limit
S A 1–5 2
Charger Depleted Battery
Voltage Target
S A
4–12
(12 V)
18–24
(24 V)
10
(12 V)
20
(24 V)
Charger Equalize Stage
Duration (Min)
Note: Equalize is only
available with FLA/VRLA
topology selected.
S A 60 – 480
Charger Manual Equalize
Cycle Activation
Note: Equalize is only
available with FLA/VRLA
topology selected.
S A
Active
Inactive
Inactive
Charger Maximum Absorption
Time Threshold (Min.)
S A
60 – 360
60 – 600
(NiCad
only)
240
Charger Maximum Bulk Time
Threshold (Min)
S A 60 – 600 480
Charger Refresh Charge Cycle
Time (Hr)
S A
0,
23 – 672
335
Charger Return To Bulk State
Voltage Threshold (V)
S A
10–13
(12 V)**
20–26
(24 V)**
12.8
(12 V)
25.6
(24 V)
Charger Starter Battery
Topology
Note: Verify that the battery
topology is set correctly for the
battery type that is used.
Incorrect charger output
system voltage may cause
irreversible damage to the
battery and abnormal out
gassing.
S A
Default
FLA/VRLA
AGM
Gel
NiCad
Default
Charger System Battery
Voltage
Note: Verify that the system
voltage is set correctly for the
battery type that is used.
Incorrect charger output
system voltage may cause
irreversible damage to the
battery and abnormal out
gassing.
S A
System 12
VDC
System 24
VDC
12 VDC
* Function requires optional input sensors or is engine ECM dependent on some generator set models.
[ ECM inputs are engine-manufacturer dependent.
] Changeable only by resetting the controller with a personality profile (SiteTech 1.4 or higher).
** Denotes the default parameter range. Typically, ranges for the NiCad battery topology are slightly wider. For more details, refer to the
battery charger operation manual.