TP-6694 7/18 51Section 2 Operation
2.7.1 Error Messages
Certain entries or attempted entries may cause the
controller to display an error message. Some of the
error messages shown here are also shown as part of
2.4.5 System Fault Warning Lamp with Digital Displays
and 2.4.6 System Fault Shutdown Lamp with Digital
Displays.
Cannot Calibrate appears when attempting to calibrate
the voltage and current values in the GenSet Calibration
menu with the unit stopped. The unit must be running in
order to make adjustments.
Cannot Edit When Stopped appears in the Voltage
Regulator menu when attempting to change the VR Volt
Adj value when the unit is not running.
Default Parameters Loaded. The fault lamp
illuminates yellow and the alarm horn sounds when the
controller detects that the default parameter settings
were loaded using SiteTecht software. The local
display shows Default Pars Warning.
ECM Address Conflict. The fault lamp illuminates red,
the alarm horn sounds, and the unit shuts down when
the controller detects an error with the ECM address.
The local display shows ECMAddr Err Shutdwn.
ECM Model Mismatch. The fault lamp illuminates red,
the alarm horn sounds, and the unit shuts down when
the controller detects an error with the ECM model. The
local display shows ECM Mismatch Shutdwn.
File System Error. The fault lamp illuminates red, the
alarm horn sounds, and the unit shuts down when the
internal controller diagnostics detect a firmware file
error. The local display shows File Error Shutdwn.
Max Alternator Current Low. The current value listed
in the maximum alternator current personality
parameter is too low compared to the kW setting within
the personality.