EasyManua.ls Logo

Kold-Draft GB564AC - Pre-Install Checklist

Default Icon
85 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
new 60 Series Service Manual.rev. 06.01.16.docx - 5 –
Pre-Install Checklist
Ambient air temperatures at the install location are between 45°F (7°C) and 90°F(32°C), the
machine must be installed indoors.
The machine will have the minimum opening sizes listed below. Heights listed are strictly the
ice machine and do not include the height of the bin. Depths listed are adjusted to
accommodate plumbing and electrical hookups.
Width
Depth
Height
Model
(in)
(cm)
(in)
(cm)
(in)
(cm)
GT36xA &
GT36xL
38
97
29
74
17
43
GT56xA &
GT56xL
38
97
29
74
32
81
GB56xA
54
137
38
97
17
43
GB56xL
54
137
29
74
17
43
GB106xA
54
137
38
97
40
102
GB106xL
54
137
29
74
40
102
GB106xRC
54
137
33
84
40
102
Each ice maker and each ice bin must enter the drain stack through separate connections.
Models equipped with a liquid condenser that does not recirculate coolant must have a drain
for each condenser that enters the drain stack through separate connections
The drain hose or pipe will remain a constant diameter from the machine to the drain
o The building drain must be able to accommodate all the drain water from the ice
machine operation.
Individual drains will not be directly connected to a common manifold, drain or standpipe. If
individual drains are to be discharged into a common manifold, drain or standpipe, a minimum
38mm (1.5”) air gap must be provided at each connection. This is to prevent any backflow of
drain water into the ice maker or ice bin.
Drain lines will be installed with a minimum drop of 1” per 3’ run (2.5cm per meter run).
The temperatures of the water supply fall between 45°F (7°C) and 90°F(32°C)
The water supply must be potable, not laden with sediment and have free chlorine levels no
greater than 0.2ppm.
A minimum 5 psig (0.034 MPa) dynamic water supply pressure is required for proper
operation of the ice maker water valve. Please note that on liquid cooled ice machines, where
the same water supply is used for both condenser cooling and the potable water supply, the
demand for condenser coolant may cause the supply pressure to drop. This is most notable
at the time of peak load, at the beginning of the freeze cycle. The maximum water supply
pressure is 100 psig (0.6 MPa).
All water lines have been purged before connection.
All KOLD-DRAFT models are intended to be installed with a permanent connection to the field
electrical supply. Drop cord connections are not to be used with this equipment. Always be
sure the power supply is the same as the ice machine’s electrical specification, which is listed
on the serial number tag on the front of the top frame cross member
Each ice maker must be connected to the grid through its own dedicated fuse or HACR type
circuit breaker.
Each ice maker must be connected to a separate protected circuit with no other loads.
Fused disconnects, installed adjacent to each ice maker, are recommended and may be
required by local codes. These components must be supplied by the installer.

Table of Contents

Related product manuals