7 Quick Start Instructions
32 of 88
BoosterControl Advanced
7 Quick Start Instructions
DANGER
Incorrect electrical installation
Danger of death from electric shock!
▷ Any work on the electrical system shall be undertaken by a trained electrician
only (DINVDE 0105 - Part1/07.83).
▷ Before commencing any work on the electrical installations, de-energise the
system and make sure it cannot be re-started unintentionally. Ensure staff
safety by PELV
3)
:
▷ Only motor protection devices with safe isolation to EN50178 (VDE0160) may
be connected directly.
CAUTION
Improper electrical connection
Damage to property
▷ All connections shall be made in accordance with the technical specifications
issued by the local energy supply companies.
▷ Check the type of current and voltage of the mains.
These quick-start instructions are designed to enable you to use the device
immediately. They are not meant to be comprehensive and are, therefore, not a
substitute for the step-by-step instructions given in the operating manual. These
quick-start instructions describe the procedure in chronological fashion. To this end,
the operating modes are covered in sequential order.
ü The setpoint for the system pressure has been factory-set to 400kPa.
Setting or converting to other units is possible at any time.
(ðSection6.4.1,Page28)
ü Note the ambient conditions. (ðSection8.1,Page34)
ü Observe the terminal assignments on the printed circuit board.
(ðSection5.4.1,Page14)
1. Mount/install BoosterControl Advanced.
2. Connect the power supply.
3. Connect/bridge motor protection or fire alert or external ON/OFF.
4. Connect the pump contactors.
5. Connect the pressure sensor/pressure switch.
6. Log in to BoosterControl Advanced at service or factory access level.
(ðSection6.6,Page31)
7. For cascade operating mode: Set parameter 3-2-2-6 to HyamatK.
8. For floating frequency inverter operating mode: Integrate and connect
frequency inverter in control cabinet.
9. For frequency inverter per pump operating mode: Connect frequency inverter.
10. Set the motor data.
For this purpose, proceed as follows, depending on the frequency inverter:
- Via the control panel of the frequency converter (refer to manufacturer's
instructions)
- Via the service software for the frequency inverter (refer to manufacturer's
instructions)
11. Set the following parameters on BoosterControl Advanced:
3) PELV = Protective Extra Low Voltage. The inputs for the thermal circuit breakers (TCBs) are not galvanically isolated from
the PELV circuits of the control inputs, 24Vdigital outputs and service interface.