8 Commissioning/Start-up/Shutdown
53 of 88
BoosterControl Advanced
This is why in a pressure booster system, long pipelines will cause the pressure to fall
below the required setpoint directly at the consumer installation.
The BoosterControl Advanced control system dynamically adapts the discharge
pressure (at the discharge header) based on the increasing flow rate so that the
required pressure is present at the consumer installation.
Log in to BoosterControl Advanced at service or factory access level.
(ðSection6.6,Page31)
Table52: Dynamic pressure setpoint compensation (DFS)
Parameter Description Possible values
3-5-10 Activate DFS (enter piping loss value) E.g. -9.99 ... 999bar
0 = deactivates the function
8.5.11 Setting freely parameterisable inputs
BoosterControl Advanced offers the option of processing remote signals. To this end,
hardware inputs WSD1 to WSD3 (J 401) must be connected properly to the remote
control signalling device.
The control system settings must then be made in accordance with the parameter list
using the service tool. (ðSection8.5.7,Page51)
Table53: Freely parameterisable inputs
Inputs WSD1 to WSD3 Action Note
Functional check run Activates a functional check run To activate a functional check run via
an external signal, in addition to the
internally programmable functional
check run. The "digital input" must be
previously selected in parameter 3-7-3.
Setpoint changeover Changeover to an alternative setpoint To activate an alternative setpoint via
an external signal, in addition to the
internally programmable setpoint.
Leakage monitoring Creates a display message Must be set in the control system (inlet
pressure monitoring with pressure
switch)
Acknowledgement Remote acknowledgement of message
Bypass valve Input for water flow detector For bypass control systems with water
flow detector
Emergency power function
(limitation of number of pumps)
Reduces system output to a defined
value
Only a defined number of pumps are
operated when emergency power is
supplied
8.5.12 Setting freely configurable outputs
BoosterControl Advanced offers the option of outputting remote signals. To this end,
hardware outputs P4 to P6 (J 104) of a BoosterControl Advanced for 6 pumps must be
connected to the remote control signalling device accordingly. The control system
settings must then be made in accordance with the parameter list using the service
tool. The number of freely parameterisable outputs is reduced in relation to the
number of pumps. For example, a 5-pump system only has one output (P6)
unassigned (in this example, 5 are reserved for controlling the pumps).
Table54: Freely parameterisable outputs
Output (P4 - P6) Action Note
Inlet tank filling Actuates an additional valve If the standard filling routine for a tank
is insufficient for the inlet tank filling
function, up to 2 additional valves can
be (ðSection8.5.3,Page46) actuated.
Inlet tank filling via motorised
gate valve
Activate "Supply level" menu item Actuates the motorised gate valve
(ðSection8.5.3,Page46)