8 Commissioning/Start-up/Shutdown
54 of 88
BoosterControl Advanced
Output (P4 - P6) Action Note
Bypass valve Actuating a bypass valve A bypass valve can be actuated during
the functional check run (only
configurable if at least one pump is
running).
Dry running protection (RDP), lack
of water
RDP message to the remote control
station
Output is switched if dry running
protection is active. (message)
8.5.13 Configuration example
Table55: Example for configuration of dry running protection
Parameter Settings
3-9 Manually
3-5-15 0,8 bar
3-5-16 1,4 bar
3-6-8 10 s
If the dry running protection settings are made as shown above (table, "Example for
configuration of dry running protection"), the system will operate as follows:
The system will be stopped by the dry running protection device when the system
pressure has dropped below 0.8bar for at least 10seconds.
When the system has been stopped by the dry running protection device, the
lack of water fault is displayed at parameter 2-1-1.
When the system pressure has increased to more than 1.4bar, the fault can be
acknowledged manually. The system then starts again.
8.5.14 Setting alternative setpoint using a timer
Log in to BoosterControl Advanced at service or factory access level.
(ðSection6.6,Page31)
Table56: Parameter settings for alternative setpoint
Parameter Description Possible values
3-7-8-1 Activate/deactivate setpoint of external input Off
Activated once daily
Activated once weekly
3-5-9 Alternative setpoint 0 ... 9999 kPa
3-7-8-2 Only if parameter 3-7-8-1 is set to "daily": 0 ... 24 h
Time of day when the alternative setpoint is to be
activated/deactivated
0 ... 60 min
3-7-8-3 Day on which the alternative setpoint is to be
activated
Sunday - Saturday
3-7-8-4 Only if parameter 3-7-8-1 is set to "weekly": 0 ... 24 h
Time of day when the alternative setpoint is to be
activated/deactivated
0 ... 60 min