EasyManua.ls Logo

KSB BoosterControl Advanced - Fire-Fighting Function; Emergency Power Function (Limitation of Number of Pumps)

KSB BoosterControl Advanced
88 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8 Commissioning/Start-up/Shutdown
51 of 88
BoosterControl Advanced
Table47: Optional settings for the water flow detector
Parameter Description Default Possible values
3-4-4-1 Number of water replacement cycles 30 1 ... 99
3-4-4-2 Period of water replacement cycles 24 h 0 ... 24 h
3-4-4-3 Average ambient temperature 25 °C 0 ... 99 °C
3-4-4-4 Measuring period for ambient
temperature
24 h 0 ... 24 h
3-6-10 Pulse length of water flow detector1 0 s Refer to table on pulse
lengths for water flow
detector
3-6-11 Pulse length of water flow detector2 4 s
3-6-12 Pulse length of water flow detector3 4 s
KSB recommends the following pulse length values for a water flow detector:
Table48: Pulse lengths for water flow detector
Accumulator size Pulse length
0 ... 50 l 0 s
50 ... 100 l 1 s
> 100 l 4 s
8.5.6 Fire-fighting function
Higher volume flow rates and pressures must be provided by the pressure booster
system in the event of a fire. When the "Fire" (J403) input is switched, all pumps start
up immediately, regardless of the protection devices fitted.
All warnings and messages output by the pump are ignored in this operating status.
(A fire alert has absolute priority.)
When the "Fire" input is restored to the original state the pumps return to their
previous operating status in line with their stop delay periods. All protective devices
and facilities then resume their operative effect.
8.5.7 Emergency power function (limitation of number of pumps)
If a building is equipped with an emergency power supply system, only a specific
number of pumps may frequently be operated simultaneously due to the limited
power supply available. This can be parameterised correspondingly in percent.
Emergency power is detected at one of inputs WSD1 to WSD3 (J 401). This is freely
configurable or can be assigned via parameter settings. When the original power
supply is restored, the pumps return to their previous operating status in line with
their start delay periods.
No automatic pump changeover is carried out as long as this function is active.
Log in to BoosterControl Advanced at service or factory access level.
(ðSection6.6,Page31)
Table49: Emergency power function (limitation of number of pumps)
Parameter Description Default Possible values
3-4-2-5 Emergency power restriction, system
load limit in %
600 0...600 %
3-8-1 Programming of digital
parameterisable inputs
DI1..3 (WSD 1..3)
3-8-1-1 Parameterisable input DI 1 (WSD1) Off Emergency power, fire
alert, alternative setpoint,
etc.
3-8-1-2 Parameterisable input DI 2 (WSD2) Off Emergency power, fire
alert, alternative setpoint,
etc.
3-8-1-3 Parameterisable input DI 3 (WSD3) Off Emergency power, fire
alert, alternative setpoint,
etc.

Table of Contents

Related product manuals