8 Commissioning/Start-up/Shutdown
48 of 88
BoosterControl Advanced
Table40: Parameter settings for alternative level
Parameter Description Default Possible values
3-4-1-4-9-3 Alternative level in the inlet tank
when the gate valve is to open
40 % 0 ... 100 %
3-4-1-4-9-4 Alternative level in the inlet tank
when the gate valve is to close
60 % 0 ... 100 %
3-4-1-4-10-2 Level (timer-controlled) in the inlet
tank at which the proportional valve
is to open
40 % 0 ... 100 %
3-7-9 Month and day when the alternative
level is enabled
Off Off
January - December
0 ... 31
3-7-10 Month and day when the alternative
level is disabled
Off Off
January - December
0 ... 31
8.5.3.3 Level detection via pressure sensor
ü Pressure sensor has been connected.
1. Log in to BoosterControl Advanced at service or factory access level.
(ðSection6.6,Page31)
Set the following parameters:
Table41: Level detection via pressure sensor
Parameter Description Default Possible values
3-3-2 Settings for the suction side
BoosterControl Advanced reboots;
observe notes
Inlet tank with gate valve Inlet tank with gate valve
Inlet tank with
proportional valve
3-4-1-4-1 Min. permissible water level in the
inlet tank, from upper edge of inlet
nozzle
0 cm 0 ... 99 cm
3-4-1-4-2 Max. permissible water level in the
inlet tank, from upper edge of inlet
nozzle
200 cm 0 ... 999 cm
3-4-1-4-3 Sensor level above tank floor 0 cm 0 ... 1000 cm
3-9 Deactivate the "No water" message in
the field list (then the fault is self-
acknowledging)
Activated Activated or deactivated
8.5.3.4 Setting the pressure sensor
Log in to BoosterControl Advanced at service or factory access level.
(ðSection6.6,Page31)
Set the following parameters:
Table42: Parameter settings for pressure sensor
Parameter Description Default Possible values
3-4-1-1 Suction side: Measured value of
pressure sensor at 4mA
0 kPa 0 ... 1000 kPa
3-4-1-2 Suction side: Measured value of
pressure sensor at 20mA
1000 kPa 0 ... 10000 kPa
8.5.3.5 Setting levels for messages
Levels triggering warnings and alerts are pre-set and can be adapted as required.
Log in to BoosterControl Advanced at service or factory access level.
(ðSection6.6,Page31)
If necessary, adapt parameters as follows: