EasyManua.ls Logo

KSB BoosterControl Advanced - Page 72

KSB BoosterControl Advanced
88 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10 Parameter list
72 of 88
BoosterControl Advanced
Parameter Description Factory setting Possible settings min. value max. value Read access right Write access right
3-8-1-1 Input 1
Configuration of input 1
None None,
forced start (check
run),
alt. setpoint,
leakage,
remote
acknowledgement,
bypass valve,
emergency power
- - Service Service
3-8-1-2 Input 2
Configuration of input 2
None None,
forced start (check
run),
alt. setpoint,
leakage,
remote
acknowledgement,
bypass valve,
emergency power
- - Service Service
3-8-1-3 Input 3
Configuration of input 3
None None,
forced start (check
run),
alt. setpoint,
leakage,
remote
acknowledgement,
bypass valve,
emergency power
- - Service Service
3-8-2 Outputs
Outputs
- - - - Service Nobody
3-8-2-1 Output 1 (P4)
Configuration of output 1
None None,
threshold 1,
threshold 2,
supply valve,
bypass valve,
lack of water
- - Service Service
3-8-2-2 Output 2 (P5)
Configuration of output 2
None None,
threshold 1,
threshold 2,
supply valve,
bypass valve,
lack of water
- - Service Service
3-8-2-3 Output 3 (P6)
Configuration of output 3
None None,
threshold 1,
threshold 2,
supply valve,
bypass valve,
lack of water
- - Service Service

Table of Contents