10 Parameter list
BoosterControl Advanced
75 of 88
Parameter Description Factory setting Possible settings min. value max. value Read access right Write access right
3-14-1 Valve Function
Activating/deactivating the valve
function
Off Off,
forced start (check
run),
PT 1000,
digital input
- - Everybody Service
3-14-2 Open delay
Delay time that lapses before valve is
opened.
2 0.. 20 0 20 Everybody Service
3-14-3 Close delay
Delay time that lapses before valve is
closed.
2 0.. 20 0 20 Everybody Service
3-14-4 Temperature
Temperature above which the valve is
opened
20 0.. 40 0 40 Everybody Service
3-14-5 Flush Time
Time window in which the valve is opened
120 10.. 600 10 600 Everybody Service
3-14-6 Attemps in 24Hrs
Valve opening frequency before an alert is
displayed
2 1.. 5 1 5 Everybody Service
3-14-7 Min. open time
Minimum opening time of valve
2 0.. 20 0 20 Everybody Service
3-15 Fieldbus
Field bus settings
- - - - Customer Nobody
3-15-1 Profibus
Profibus settings
- - - - Customer Nobody
3-15-1-1 PB Slave Address
Profibus slave address
126 1.. 255 1 255 Customer Customer
3-15-2 Modbus
Modbus settings
- - - - Customer Nobody
3-15-2-1 MB Slave Address
Modbus slave address
247 1.. 247 1 247 Customer Customer
3-15-2-2 Baudrate
Baud rate
192 9600,192 - - Customer Customer
4 Info
Information
- - - - Everybody Nobody
4-1 Device
Control module (CM)
- - - - Everybody Nobody
4-1-1 Serial Number
Serial number of control module
- - - - Everybody Nobody
4-1-2 Parameter Set
Version of the control panel parameter set
0 - - - Everybody Everybody