Parameter Description Factory
setting
Setting Unit Access level Possible settings
EP MP Min. Max.
3-3-2-7
Rated I²t
Nominal value, I2t
100 100 100 150 - Factory -
3-3-4
Start Adjust
Submenu for
displaying startup
settings
- - - - - - -
3-3-4-1
Start Delay
Selection of start
time delay
0.1 0.1 0 60 s Customer -
3-3-4-2
Start Out Freq
Selection of start
output frequency
0 0 0 10 % Customer -
3-3-5
Motor Temp
Submenu for
displaying motor
temperature
- - - - - - -
3-3-5-1
Thermal Protect
Activate/deactivate
thermal motor
protection
2 2 - - - Customer No Protection
PTC Protection
3-3-5-2
Thermal Limit
Selection of limit
value of thermal
motor protection
83.5 83.5 0 100 % Service -
3-3-6
Ramps
Ramps
- - - - - - -
3-3-6-1
Ramp 0 up/down
Ramp used to reach
minimum frequency
from 0 and vice
versa
3 3 0.5 600 s Customer -
3-3-6-2
Ramp 1 Up-tm
Ramp 1 used to go
from start frequency
to setpoint
frequency
3 3 0.5 600 s Customer -
3-3-6-3
Ramp 1 Down-tm
Ramp 1 used to go
from setpoint
frequency to stop
frequency
3 3 0.5 600 s Customer -
3-3-6-4
Ramp 2 Up-tm
Ramp 2 used to go
from start frequency
to setpoint
frequency
3 10 0.5 600 s Customer -
3-3-6-5
Ramp 2 Down-tm
Ramp 2 used to go
from setpoint
frequency to stop
frequency
3 10 0.5 600 s Customer -
3-3-6-6
R1/2 Start Freq
Frequency to
change from ramp 0
to ramp 1/2
50 50 0 100 % Customer -
3-3-6-7
R1/2 Stop Freq
Frequency to
change from ramp
1/2 to ramp 0
50 50 0 100 % Customer -