Parameter Description Factory
setting
Setting Unit Access level Possible settings
EP MP Min. Max.
3-6-3-5
An IN 2 Low
Selection of lower
limit value for
analog input
monitoring
0 0 3-8-3-7 3-8-3-8 3-8-3-6 Customer -
3-6-3-6
An IN 2 High
Selection of upper
limit value for
analog input
monitoring
100 100 3-8-3-7 3-8-3-8 3-8-3-6 Customer -
3-6-3-7
An IN2 Wrn TDly
Time delay for
function
5 5 0 60 s Customer -
3-6-3-8
An IN 2 Wrn Fnc
Analog input
monitoring function
1 1
- - Customer No Function
Warning
Stop & Trip
3-6-4
Load Warnings
Submenu for
displaying load-
dependent warnings
- - - - - - -
3-6-4-1
Hi Ld @ Lo Mo F
Selection of
overload at low
motor frequency
60 60 0 3-6-4-2 % Customer -
3-6-4-2
Hi Ld @ Hi Mo F
Selection of
overload at high
motor frequency
90 90 3-6-4-1 100 % Customer -
3-6-4-3
Hi Load Profile
Selection of
overload profile
1 1 - - - Customer Linear
Square
Cubic
3-6-4-4
Hi Load Tm Dly
Selection of
overload time delay
5 5 0 30 s Customer -
3-6-4-5
High Load Fnc
Selection of
overload functions
1 5 - - - Customer No Function
Warning
Stop & Trip
3-6-4-6
Lo Ld @ Lo Mo F
Selection of low
load at low motor
frequency
30 30 0 3-6-4-7 % Customer -
3-6-4-7
Lo Ld @ Hi Mo F
Selection of low
load at high motor
frequency
60 60 3-6-4-6 100 % Customer -
3-6-4-8
Lo Load Profile
Selection of low
load profile
1 1 - - - Customer Linear
Square
Cubic
3-6-4-9
Lo Load Tm Dly
Selection of low
load time delay
10 10 0 30 s Customer -
3-6-4-10
Low Load Fnc
Selection of low
load functions
1 2 - - - Customer No Function
Warning
Stop & Trip
3-6-5
Setpoint Warns
Submenu for
setpoint monitoring
- - - - - - -
3-6-5-1
Min Setpoint
Selection of low
limit value for
setpoint monitoring
0 0 0 3-5-1-3 3-2-2-1 Customer -
10 Parameter lists
118 of 162