EasyManua.ls Logo

KSB PumpDrive - 7.1.1.3 Open-loop control mode

KSB PumpDrive
162 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
bar is used, this range corresponds to an actual value signal range of 0 - 100 %. If the
required setpoint is, for example, 4.5 bar, a setpoint of 75 % would have to be
specified. The unit of setpoint and actual value is defaulted to [%].
Table 48: Parameters for unit of setpoint and actual value
Parameter Description Possible settings Factory setting
3-2-2-1
Physical unit of setpoint Selection list III (Section 10.1
Page 129)
1
3-2-2-2
Physical unit of flow rate (Q) 29
3-2-2-3
Physical unit of pressure 1
3-5-1-3
Maximum setpoint For unit %: Select 100 %
For units bar, m, m
3
/h,...: Set to
full-scale value of the sensor,
e.g. 6 bar
100
7.1.1.3 Open-loop control mode
In open-loop control mode, PumpDrive translates the specified setpoint into the
corresponding motor speed. The process controller is deactivated. PumpDrive starts
up in automatic mode if digital input 1 is supplied with +24 V DC (terminal strip
P4:13/14). Circuit diagram (Section 9 Page 99)
GN
D
DI6
DI5
DI4
DI3
DI2
DI1
+24V
AGND
AN-OUT
20191817161514131211
1
AGND
AIN1
GND
AIN2
+24
V
NO2
CO
M2
NO1
COM1
10931 2 4 5 6 7 8
P4
P7
2
0V
S ignal
3 4
Fig. 25: Terminal wiring diagram, open-loop control mode (dashed line = optional)
1 Start/stop 2 External setpoint signal
(Section 7.1.1.2 Page 49)
3 Signal relay 1
(Section 7.4.2 Page 95)
4 Signal relay 2
(Section 7.4.2 Page 95)
Table 49: Open-loop control mode
Function Input/connection Specification Setting range/parameter value
Setpoint
specification
P7 terminal strip Analog input 1 (P7: 9/10) 5-10 V DC 25-50 Hz
Graphical control panel Configurable setpoint
(3-5-2-1)
50 - 100 % 25 - 50 Hz
Standard control panel (Section 6.1.5 Page 39) 50 - 100 % 25 - 50 Hz
Field bus See field bus module literature
Start
command
P4 terminal strip Digital input 1 (P4: 13/14) Start in automatic mode
Field bus See field bus module literature
Process
controller
Graphical control panel PI Auto (3-9-1-6) Deactivated
Process
controller
Graphical control panel PI mode (3-9-1-1) Disabled
Operating
mode
Graphical control panel MAN-OFF-AUTO AUTO
7 Commissioning/shutdown
PumpDrive
51 of 162

Table of Contents

Related product manuals