EasyManua.ls Logo

KSB PumpDrive - Page 52

KSB PumpDrive
162 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7.1.1.3.1 Open-loop control mode using external standard signal
By default, analog input 1 (terminal P7:9 AnIn1 and 10 AGND P7) is set as the
setpoint source (
3-5-4-1
). A direct voltage of 0 to 10 V (0 to 100 %) is expected as the
signal. If a current signal, e.g. 4 - 20 mA (0 - 100 %) is to be used, the Anln1 Setting
parameter (
3-8-2-1
) has to be set to Current. The setpoint input can be adapted to
the signal by using the parameters
3-8-2-2
to
3-8-2-5
. At a setpoint ≤ 50 %,
PumpDrive always operates at a minimum frequency of 25 Hz (
3-6-1-2
: 50 %) set in
the factory. If the setting range of the setpoint signal is to apply from the minimum
frequency (
3-6-1-2
) on, the AnIn 1 Low parameter (
3-8-2-7
) has to be set to 50 % and
the corresponding unit.
At analog input 1, a setpoint of 78 % is to be set via a 0 - 10 V voltage signal. 7.8 V
then corresponds to a speed of 39 Hz (
3-11-4-1
maximum output frequency = 50 Hz)
Table 50: Sample parameterisation of analog input 1
Parameter Description Settings Factory setting
3-2-2-1
Setpoint unit % %
3-2-2-3
Pressure unit % %
3-5-1-2
Minimum setpoint 0 0
3-5-1-3
Maximum setpoint 100 100
3-5-4-1
Setpoint source 1 Analog IN 1 Analog IN 1
3-5-4-2
Setpoint source 2 None Configurable Setpoint
3-5-4-3
Setpoint source 3 None Remote Setpoint
3-8-2-1
AnIn 1 setting Voltage Current
3-8-2-2
Analog IN 1 Low voltage 0 0
3-8-2-3
Analog IN 1 High voltage 10 10
3-8-2-6
Unit of Analog IN 1 % %
3-8-2-7
Low value for Analog IN 1 0 0
3-8-2-8
High value for Analog IN 1 100 100
3-9-1-1
PI mode Disabled Disabled
3-9-1-6
PI Auto Deactivated Activated
Maintain the following sequence for deactivating the process controller:
1.
Change parameter
3-9-1-6
.
2. Change parameter
3-9-1-1
.
The value displayed for parameter
1-3-1-3
Setpoint is 78 %.
7.1.1.3.2 Open-loop control mode via control panel
Graphical control panel
The speed setpoint can be specified using the control panel. For this purpose, the
Setpoint Source 2 parameter
(3-5-4-2)
must be set to Configurable Setpoint (factory
setting).
The setpoint is specified using the Configurable Setpoint parameter
(3-5-2-1)
. The
setpoint unit is set using the Setpoint Unit
(3-2-2-1)
and Max Setpoint
(3-5-1-3)
parameters (Section 7.1.1.2 Page 49) .
A 2-pole motor is to run with a speed of 2500 rpm. This corresponds to a frequency
of 41.67 Hz. A setpoint of 83.33 % must be set at the control panel for this purpose.
(for
3-11-4-1
maximum output frequency = 50 Hz)
n
n
-
n
(
-
)
= [%]
2500
1
3000
1
- 1500
1
(
100% - 50%
)
= 83,33%
Target
Target
Target
Target
Max.
Max.
Min.
Min.
Min.
Min.
Min.
Fig. 26: Sample calculation
Table 51: Sample parameterisation of open-loop control mode via control panel
Parameter Description Settings Factory setting
3-2-2-1
Setpoint unit % %
3-2-2-3
Pressure unit % %
Example
Example
7 Commissioning/shutdown
52 of 162
PumpDrive

Table of Contents

Related product manuals