EasyManua.ls Logo

KSB PumpDrive - Page 88

KSB PumpDrive
162 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table 91: Parameterisation for the dynamic pressure compensation function on a PumpDrive Advanced model using
flow rate estimation based on the power
Parameter Description Settings
3-9-1-5
Process type of PI controller Variable Pressure
3-4-1-1
Q measurement/estimate Measured
3-12-1-1
Q measurement P/Q calculated
3-4-1-3
Calibration for Q measurement, p 100 % value Full-scale value of pressure/differential pressure
sensor
3-4-2-1
Q compensation point As required by system conditions
3-4-2-2
Setpoint compensation
Parameters
3-12-3-7
to
3-12-3-20
for the pump's H/Q curve described in section must
be set for parameterisation of the dynamic pressure setpoint compensation function
on a PumpDrive Advanced model using flow rate estimation based on the
differential pressure. Also read the information provided in the relevant section for
parameterising the flow rate estimation function (Section 7.2.2.3.1 Page 80) . The
differential pressure measurement can either be effected by a differential pressure
sensor or two pressure sensors in the discharge-side and suction-side piping.
Therefore, the following parameters are required in addition to the parameters listed
for defining the analog inputs:
Table 92: Parameterisation for the dynamic pressure setpoint compensation function on a PumpDrive Advanced
model using flow rate estimation based on the differential pressure
Parameter Description Possible settings Factory setting
3-8-2-11
AI 2 descriptor Process
Pressure P1
Pressure P2
Q
Temperature
Process
3-8-3-11
AI 2 descriptor Process
The parameters must be set as follows:
Table 93: Parameterisation for the dynamic pressure setpoint compensation function on a PumpDrive Advanced
model using flow rate estimation based on the differential pressure
Parameter Description Settings
3-9-1-5
Process type of PI controller Variable pressure
3-4-1-1
Q measurement/estimate Measured
3-12-1-1
Q measurement P/Q calculated
3-4-1-3
Calibration for Q measurement, p 100 % value Full-scale value of pressure/differential pressure
sensor
3-4-2-1
Q compensation point As required by system conditions
3-4-2-2
Setpoint compensation
NOTE
The differential pressure sensor, if used, is always connected to analog input 2. The
AI 1 descriptor parameter
(3-8-2-11)
must not be set to Pressure P1.
Table 94: Parameterisation of analog inputs for connection of a differential pressure sensor
Parameter Description Settings
3-8-2-11
AI 1 descriptor Process
3-8-3-11
AI 1 descriptor Pressure P2
Connection of a suction pressure sensor to analog input 1 and a discharge pressure
sensor to analog input 2.
Table 95: Parameterisation of analog inputs for connection of a suction pressure sensor
Parameter Description Settings
3-8-2-11
AI 1 descriptor Pressure P1
3-8-3-11
AI 1 descriptor Pressure P2
The parameters for parameterisation of the dynamic pressure compensation function
on a PumpDrive Basic model using flow rate measurement via a sensor must be set as
follows:
7 Commissioning/shutdown
88 of 162
PumpDrive

Table of Contents

Related product manuals