73
8 Options
DIP switch settings
Terminal assignment:
10 / 11 / 12 Pt100 temperature input for recording the flue gas temperature 0 ... 400 °C
7 / 8 / 9 Pt100 temperature input for recording the inlet temperature 0 ... 400 °C
3+ / 3- Analogue output 3 efficiency
Factory setting: 80 ... 100% 4 ... 20 mA
4+ / 4- Analogue output 4 (flue gas temperature)
Factory setting: 0 ... 400°C 4 ... 20 mA
DIP switch 1
LSB terminal resistance 120
ON active (terminal device)
DIP switch 1
LSB terminal resistance 120
OFF not active
DIP switches 2 and 3
LSB device family 2 (Standard)
2 OFF 3 OFF
DIP switches 2 and 3
LSB device family 2
2 ON 3 OFF