▶ DX2‑T1:
LED states Descripon
O Temperature is in the normal state.
Flashing
(1 ash and 1 o)
Temperature enters either alarmed state: warning or
crical.
High-speed ashing Sensor rmware is being updated. See Sensor Firmware
Update (on page 58).
▶ DX2‑T1H1:
LED states Descripon
O Both temperature and humidity are in the normal
state.
Flashing
1 ash and 1 o Temperature enters an alarmed state: warning or
crical.
Humidity is in the normal state.
2 ashes and 1 o Temperature is in the normal state.
Humidity enters an alarmed state: warning or
crical.
3 ashes and 1 o Both temperature and humidity enter an alarmed
state: warning or crical.
High-speed ashing Sensor rmware is being updated.
DX2-T1DP1 - Temperature and Dierenal Air Pressure Sensors
DX2-T1DP1 detects temperature and dierenal air pressure. This sensor is designed to receive the
inputs of two pressure levels. Dierenal air pressure is measured by reading the dierence of the two
inputs.
DX2-T1DP1 sensor packages come with one DX2-T1DP1 sensor and 2 tubes for connecng to the air
pressure nozzles.