DX2T1:
LED states Descripon
O Temperature is in the normal state.
Flashing
(1 ash and 1 o)
Temperature enters either alarmed state: warning or
crical.
High-speed ashing Sensor rmware is being updated. See Sensor Firmware
Update (on page 58).
DX2T1H1:
LED states Descripon
O Both temperature and humidity are in the normal
state.
Flashing
1 ash and 1 o Temperature enters an alarmed state: warning or
crical.
Humidity is in the normal state.
2 ashes and 1 o Temperature is in the normal state.
Humidity enters an alarmed state: warning or
crical.
3 ashes and 1 o Both temperature and humidity enter an alarmed
state: warning or crical.
High-speed ashing Sensor rmware is being updated.
DX2-T1DP1 - Temperature and Dierenal Air Pressure Sensors
DX2-T1DP1 detects temperature and dierenal air pressure. This sensor is designed to receive the
inputs of two pressure levels. Dierenal air pressure is measured by reading the dierence of the two
inputs.
DX2-T1DP1 sensor packages come with one DX2-T1DP1 sensor and 2 tubes for connecng to the air
pressure nozzles.