25
EquipmEnt
Selections listed in this section are dependent on system hardware conguration.
Not all options will be available.
NOTE: When changing the default settings for any parameter, there is a possibility
that it will affect the settings for another parameter. If this happens, a pop-
up message will be displayed listing the other affected parameters and
their new automatically set values.
equipment name
display
filter 1 timer selection
filter 2 timer selection
uv bulb timer selection
zone 1
zone 2
zone 3
continues blower cmf
alerts
name
Changing Temperature Control Mode
warning
ok
has affected the following parameters:
new value
Temperature Control
Mode
Wall Insulation
2
1
Figure 18. Parameter Update Notication
Smart Hub
The following is a complete list of all possible parameters under System. Parameters
actually available are dependent on the Smart Hub settings.
Smart Hub Parameters
Parameter Description
About
This screen provides information concerning language
supported, equipment type name, control software
revision, model, control mode number, control serial
number, control hardware revision, protocol revision
number, device product level, 24VAC average power
consumption, 24VAC peak power consumption,
compatible devices list, application code memory size and
micro-controller part number.
Smart Hub Parameters
Parameter Description
Auto Changeover -
Humidif. Deadband
Prevents the Humidication and Dehumidication settings
from being closer together than 5% or greater than 10%
(Dead-band).
Range is 5 to 10%. Default is 5%. Adjustments are in
increments of 1%.
Auto Changeover -
Temp Deadband
Prevents the Heating and Cooling from being set closer
together than 3ºF (1.67°C) or greater than 9ºF (5.0°C)
(Dead- band).
Range is 3 to 9°F (1.67 to 5.0°C). Default is 3°F (1.67°C).
Adjustments are in increments of 1°F (0.56°C).
Auto
Dehumidication
Overcooling
Threshold
Range is 0 - 10%. Default is 4%. Adjustments are in
increments of 1%. This value can automatically be
affected by adjusting other parameters. One example
would be when enabling Max Dehumidication
Overcooling.