EasyManua.ls Logo

Lennox icomfort Touch - Setting up Equipment parameters; Stage Delay & Differential Settings (Installer settings)

Lennox icomfort Touch
44 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
506566−01 09/10
Page 12
Setting up Equipment parameters
This feature allows the installer to edit details of devices in the
system without having to re−run the setup program. When the
press start..." screen appears, press start. The Equipment
details edit" screen (figure 30) will open. You may view infor-
mation about or modify communicating devices as described
earlier in the setup pages, beginning on page 10. Use the ar-
rows to select a device and press edit.
next step
edit
reset all
about
setup tests equipment HELP
to adjust a device,
highlight it, then press
edit
system devices
press start button below to edit details of devices
in the system
start
HP
XP17−036−230−01
5910M12345
Furnace
SLP98UH−
090V36C−01
5910G17546
Thermostat
49W95
A110A00070
Figure 30. Equipment details edit
Use the arrows to highlight a settings and then press edit (fig-
ure 31). In the example (figure 32), the heating airflow may be
changed from the default (Fixed CFM) to Fixed DAT. If you
make a change, press save.
Changes may affect other settings and, if so, those setting will
appear in red and require changing/saving to clear the red
settings.
setup tests equipment HELP
Equipment Name
Heating Airflow
Control Type
Low Heating
Airflow
High Heating
Airflow
to adjust a setting, high-
light it, then press edit
Current Value:
Fixed CFM
Furnace
back
edit reset
Figure 31. Equipment details edit
default is underlined
current value is checked
savecancel
Fixed CFM
Fixed DAT
Figure 32. Changing a device’s setting
Table 2 on (on Page 21) shows a list of Editable Parameters
for the currently available devices designed to communicate
in this system. Other devices and additional parameters may
be added at a later date. Check the unit installation manuals
(i.e. furnace, air handler, heat pump, ac unit) for current infor-
mation and default parameters.
Stage Delay & Differential Settings (Installer
settings)
1st Stage DifferentialStage 1 differential is used in all ther-
mostats. The default is 1.0°F but can be programmed be-
tween 0.5° and 3.0°F in 0.5°F increments.
From the equipment tab, use the arrows to select 1st Stage
Differential. Press edit. Use the up/down arrows to adjust to
the desired setting and press save.
2nd Stage Differential (where applicable)The default is
1.0°F but can be programmed between 0.5° and 8.0°F in
0.5°F increments.
3rd Stage Differential through 6th Stage Differential
(where applicable)The default is 0.5°F but can be pro-
grammed between 0.5°F and 8.0°F in 0.5°F increments.
NOTE − Each stage’s differential is based on the previous
stage’s differential endpoint. For example, in cooling mode, if
stage 1 differential is set to 1.0ºF, then the system comes on
0.5ºF above setpoint and the 2nd differential starts at the
0.5ºF stage 1 endpoint and extends to 2nd stage differential
endpoint.
NOTE − In normal operation, the end of the cooling demand is
at the setpoint −0.5ºF and the end of the heating demand is at
the setpoint + 0.5ºF.
Staged Delay Timersdefault Enabled. When ON, all stage
delay timers (stages 2 through 6) are enabled and will serve to
bring on additional stage(s) of cooling or heating on a timed
basis (default 20 minutes) in cases when the previous stage
of heating or cooling will not raise or lower the room tempera-
ture to the set point in a given time.
When Disabled is selected all stage delay timers are dis-
abled. This means stages are changed based on the temper-
ature and not their timer delays.
NOTE − The 2nd Stage Delay Timer (when Staged Delay Tim-
ers is Enabled) is used for both HEATING and COOLING.
However, if the system has a modulating furnace, 2nd Stage
Delay Timer will only be used for COOLING (not for heating,
as the modulating algorithm ignores delay timers).
2nd thru 6th Stage Delay timer (where applicable)If
Staged Delay Timers are Enabled, the default delay is 20 min-
utes but can be programmed from 5 to 120 minutes in 5−min-
ute increments. If first stage fails to advance the ambient tem-
perature toward the setpoint by 1.0°F in the programmed
delay time, then the second stage is activated.
Heat Cool Stages Locked Indefault Disabled (heat/cool
stages are turned off separately). If changed to Enabled,
heat/cool stages are turned off together. Scroll to Heat Cool
Stages Locked In; press edit. Use arrows to select between
Disabled or Enabled. Press save.

Related product manuals