Page 36
Configuring heat strips on Air Handler Control (AHC)
IMPORTANT: After electric heat strips are installed, the Air
Handler Control (AHC) must be manually configured to detect
the number of electric heat sections. (SEE ALSO 506181−01
for complete configuration guide.)
To configure the heat strips so that they will be detected by the
thermostat:
Power must be applied to the air handler but NOT to the
thermostat. Remove thermostat faceplate or remove
wires to thermostat at the air handler.
On the air handler control (AHC), unit should be in idle
mode (decimal blinks at 1 Hertz0.5 second ON, 0.5
second OFF.
Select field test modepress and hold the pushbutton
until solid –" appears; release button. Display will blink.
Press the pushbutton and wait for the display LED to
show H" (capital H), then release the button.
The AHC cycles the indoor blower motor "on" to the se-
lected heat speed and stages the electric heat relays on"
and off´ to automatically, detecting the number of electric
heat sections. The AHC stores the number of electric
heat sections, then automatically exits Field Test Mode".
At this point, the icomfort Touch will now detect the heat
strip information stored in the AHC.
OUTDOOR
AIR SENSOR
HEAT
1234
COOL
1234
DELAY
12 34
ADJUST
NORM +
HUMIDIFICATION
SMART
AUTO
EVENHEAT
1234
BLOWER
ONLY CFM
100
11 5
130
85
Y1Y2
2STAGE
COMPR
RO
HEAT
PUMP
RDS
DEHUM
OR
C
W1
W2
G
Y2
Y1
C
R
DH
H
L
O
DS
W3
FUSE 3 AMP
XFMR 24V
24 VAC
COM
3
6
9
1
4
7
XFMR LINE
G
2
5
8
P8
L1
L2
L2 L1
INDOOR
BLOWER
POWER
EARTH
INDOOR BLOWER
SIGNAL
4
5
6
12 3
A92
INTEGRATED
CONTROL
OUTDOOR UNIT
LINK
I + I
I + I RC
I + I
R
C
THERMOSTAT
HUMIDITROL
DH
DISCHARGE
AIR SENSOR
HARMONY
PUSHBUTTON LED