icomfort Touch 7−Day Programmable Communicating Thermostat
Page 21
Table 2. Adjustable Parameters Table (Installer)
Parameter Name: Default Parameter Value Setting Increment
Installer
entry
SYSTEM (Go to EQUIPMENT tab and scroll to SYSTEM 49W95.) NOTE − All of the following changes are made on the stat.
Equipment Name (Typewriter input screen)
Filter 1 Timer Selection Calendar Time Calendar Time, Run Time
Filter 2 Timer Selection Calendar Time Calendar Time, Run Time
Humidifier Pad Timer Selection Calendar Time Calendar Time, Run Time
UV Bulb Timer Selection Calendar Time Calendar Time, Run Time
PureAir Timer Selection Calendar Time Calendar Time, Run Time
Smooth Setback Recovery Enabled Enabled, Disabled
Electric Heat Control Mode Standard Standard, Even Heat
Gas Heat Control Mode
Modulating
(variable capac-
ity)
Staged, Modulating (variable capacity)
Autochangeover Temp Deadband 5ºF 3 to 9ºF 1ºF
Max Heat set point 90ºF 40 to 90ºF 1ºF
Min Cool set point 60ºF 60 to 99ºF 1ºF
Heat/Cool Stages Locked In Disabled Enabled, Disabled
*1st Stage Differential 1.0ºF 0.5 to 3ºF 0.5ºF
*2nd Stage Differential 1.0ºF 0.5 to 8ºF 0.5ºF
*3rd Stage Differential 0.5ºF 0.5 to 8ºF 0.5ºF
*4th Stage Differential 0.5ºF 0.5 to 8ºF 0.5ºF
*5th Stage Differential 0.5ºF 0.5 to 8ºF 0.5ºF
*6th Stage Differential 0.5ºF 0.5 to 8ºF 0.5ºF
Stage Delay Timers Enabled Enabled, Disabled
*2nd Stage Delay 20 Minutes 5 to 120 Minutes 5 Min
*3rd Stage Delay 20 Minutes 5 to 120 Minutes 5 Min
*4th Stage Delay 20 Minutes 5 to 120 Minutes 5 Min
*5th Stage Delay 20 Minutes 5 to 120 Minutes 5 Min
*6th Stage Delay 20 Minutes 5 to 120 Minutes 5 Min
Locked in 2nd Stage HP by Out-
door Temp
Off Off, 40F (4C), 45F (7C), 50F (10C), 55F (13C)
*Number of stages shown in thermostat is dependent on equipment that is installed. Electric heat will bring on 2 elements at a time if
available.
SYSTEM (continued) NOTE − All of the following changes are made on the stat.
Balance Point Control Disabled Enabled, Disabled
High Balance Point 50ºF −17ºF to 75ºF 1ºF
Low Balance Point Control 25ºF −20ºF to 72ºF 1ºF
Defrost Target Discharge Temp 55ºF 50 to 60ºF 1ºF
Dehumidification Control Mode Display Only
Display Only, Basic, Precision, Humiditrol,
Auxiliary Dehumidifier
Humidification Control Mode Display Only Display Only, Basic, Precision, Dew Point Control
Autochangeover Humidification
Deadband
5% 5 to 10% 1ºF
Max Humidification set point 45% 15 to 45% 1ºF
Max Dehumidification set point 40% 40 to 60% 1ºF
OK/Humid Boundary 50% 45 to 60% 1ºF
table continued on next page