Table 2. Adjustable Parameters Table (Installer)
Parameter Name:
Installer
entry
IncrementParameter Value SettingDefault
OUTDOOR EQUIPMENT (Go to EQUIPMENT tab and scroll to HEAT PUMP or AIR CONDITIONER.)
Equipment Name (HP & AC) Outdoor Unit
(Typewriter input screen = up to 35 characters in
string)
Compressor Short Cycle Delay
(HP and AC)
300 Seconds 60 to 300 Seconds 60 Sec
Compressor Shift Delay On/Off
(HP only)
On On, Off
Defrost Termination Temp (HP
only)
50ºF 50 to 100ºF 10ºF
AIR HANDLER
Equipment Name Air Handler (Typewriter input screen)
Electric Heating Airflow
nnnn CFM
(See Note 3 at
end of table)
NOTE: CFM Default and Values Settings are de-
pendent on the tonnage of the unit
5CFM
Low Cooling Airflow 5CFM
High Cooling Airflow 5CFM
Cooling Airflow Profile 1
1: No Delays,
2: ON: No delays; OFF: 45 sec delay
3: ON: 82%/7.5min; OFF: No delays
4: ON: 50%/30s,82%/7.5min; OFF:50%/30s
Low Heating Airflow
nnnn CFM
(See Note 3 at
end of table)
NOTE: CFM Default and Values Settings are de-
pendent on the tonnage of the unit
5CFM
High Heating Airflow 5CFM
Continuous Indoor Blower Airflow 10CFM
Humidification Airflow 10CFM
Dehumidification Airflow 70%
60 to 80% (percentage of reduction of High Cool-
ing Airflow)
1%
Delays:
Heating Indoor Blower OFF
10 sec 0 to 10 Seconds 1 sec
Heating Indoor Blower ON 0 sec 0 to 5 Seconds 1 sec
Cooling Indoor Blower OFF 0 sec 0 to 30 Seconds 2 sec
Cooling Indoor Blower ON 2 sec 0 to 10 Seconds 1 sec
HP Indoor Blower OFF 45 sec 0 to 60 Seconds 5 sec
HP Indoor Blower ON 0 sec 0 to 30 Seconds 5 sec